Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Tam veri sayfasını PDF olarak indirin:
Ürün Açıklaması |
---|
Ethernet IO-Link master with PROFINET S2 redundancy |
General specifications | ||
---|---|---|
UL File Number | E223772 | |
Functional safety related parameters | ||
MTTF | 582 a | |
Indicators/operating means | ||
LED indication | see manual | |
Rotary switch | Setting the fieldbus protocol | |
Electrical specifications | ||
Rated operating voltage | 18 ... 30 V | |
Nominal voltage | 24 V DC | |
Current consumption | typ. 200 mA | |
Current loading capacity | Max. 2 x 16 A per module (Loop-through current via L-coded power supply) Total current: max. 9 A per module |
|
Galvanic isolation | between US and UL | |
Interface 1 | ||
Interface type | Industrial Ethernet | |
Physical | M12, D-coded | |
Protocol | PROFINET IO with media redundancy protocol (MRP) and S2 system redundancy. EtherNet/IP with Device Level Ring (DLR) | |
Transfer rate | 10/100 Mbps | |
Inputs/Outputs | ||
Number/Type | 4 x IO-Link Class A (X1 – X4) 4 x IO-Link Class B (X5 – X8) Configurable as: max. 8 IO-Link and 4 digital inputs and outputs max. 12 digital inputs and 4 digital outputs max. 12 digital outputs and 4 digital inputs short-circuit protected |
|
Sensor supply | max. 500 mA per port (X1 - X8) via L+ (pin 1) | |
Output current | max. 500 mA per port (X1 - X8) Via C/Q (pin 4) In addition, a maximum of 2 A per port (X5 – X8) Via UAux (pin 2) |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | Type 1 according to IEC 61131-2 | |
Emitted interference | EN 61000-6-4:2007+A1:2011 | |
Noise immunity | EN 61000-6-2:2005 | |
Shock resistance | EN 61131-2:2004 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Cold start temperature | -40 °C (-40 °F) | |
Relative humidity | max. 95 % | |
Altitude | 0 ... 2000 m | |
Shock and impact resistance | 50 g, 11 ms, all axes | |
Vibration resistance | 15 g at 5 - 500 Hz | |
Pollution degree | 3 | |
Mechanical specifications | ||
Contact elements | PA | |
Degree of protection | IP65 / IP67 / IP69K | |
Connection | Power Supply M12, L-coded Fieldbus M12, D-coded Inputs/Outputs M12, A-coded |
|
Material | ||
Contacts | CuSn, gold-plated CuNi, gold-plated |
|
Housing | Diecast zinc | |
Seal | FKM | |
Mass | 500 g | |
Tightening torque, fastening screws | 1 Nm | |
Tightening torque, cable gland | 0.6 Nm | |
Dimensions | ||
Height | 200 mm | |
Width | 59.6 mm | |
Length | 21 mm | |
Construction type | Field housing | |
Tightening torque of clamping screws | 0.5 Nm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242608 |
ECLASS 12.0 | 27242608 |
ECLASS 11.0 | 27242608 |
ECLASS 10.0.1 | 27242608 |
ECLASS 9.0 | 27242608 |
ECLASS 8.0 | 27242608 |
ECLASS 5.1 | 27242608 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
The module is a multiprotocol fieldbus module with 4 type A and 4 type B IOLink master ports according to IO-Link standard V1.1.
The design in fully cast metal housing is resistant to mechanical damage and due to its high degree of protection to environmental influences.
The fieldbus module serves as an interface between the controller of a fieldbus system and the field level. Thanks to its multiprotocol capability, the fieldbus module supports the Ethernet communication protocols PROFINET and EtherNet/IP.
For applications with the highest demands on system availability, the module supports PROFINET S2 system redundancy when used in a PROFINET network. The module can thus simultaneously establish an application relationship (AR) to two PROFINET controllers.
An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A. The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug.
The communication protocols are configured either manually via a rotary switch or automatically. Status information for each channel is displayed via LEDs as a diagnostic function. An integrated web server enables access to the fieldbus module. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured.
Literature | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Application Report - Industrial Communication - IO-Link Master - CNC Machines | ENG | 757 KB | |
Product Information - Ethernet IO Modules with IO-Link Master | ENG | 499 KB |
Safety and Security Documentation | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Safety Datasheet / Sicherheitsdatenblatt | ALL | 383 KB | |
Manuals | |||
Manual | ENG | 4600 KB |
CAD | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 12400 KB |
CAE | |||
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 71 KB |
Certificates | Sertifika No. | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|---|
Canada, USA UL | CoC E223772 RptRef E223772-20170316 | ALL | 240 KB | |
PNO Certificate of Conformity | Z12767 | ALL | 86 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-3185CTUR | TUR | 198 KB | |
UK Declaration of Conformity (P+F) | TDOC-7493_ENG | ENG | 172 KB |
Device Description Files/Drivers | Sürüm Bilgileri | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Description files for use with Ethernet/IP Protocol and RSLogix 5000 / Studio 5000 V20 or higher / Beschreibungsdateien für EtherNet/IP und RSLogix 5000 / Studio 5000 | 05/2019 | ZIP | 13620 KB |
EtherNet/IP EDS-Files / EtherNet/IP EDS-Dateien | 04/2019 | ZIP | 73 KB |
PROFINET GSDML-Files / PROFINET GSDML-Dateien | 03/2020 | ZIP | 17 KB |
Commissioning IO-Link-Parameterization for TIA Portal V15 / Inbetriebnahme IO-Link-Parametrierung für TIA Portal V15 | 2019-06 | ZIP | 1409 KB |
Simplified AOIs (Add On Instructions) for Rockwell Automation Studio 5000. Read and Write a single parameter on an ICE1, ICE2, ICE11 or Allen Bradley IO-Link masters / Inbetriebnahmedatei_a | 2.0 Dec 19, 2023 | ZIP | 56091 KB |
Software Tools | |||
IOLM (IO-Link Master Description) for the IO-Link Device Tool from TMG TE / IOLM (IO-Link Master Description) für das IO-Link Device Tool von TMG TE | 2019-11 | ZIP | 63 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|