General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Rated current | < 35 mA | |
Power consumption | < 0.8 W | |
Input | ||
Connection side | control side | |
Connection | terminals 10+, 11- | |
Test pulse length | max. 2 ms from DO card | |
Input current | 40 mA at 19 ... 30 V DC | |
Signal level | 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC |
|
Power consumption | < 1.2 W | |
Operating mode | loop powered | |
Output | ||
Connection side | field side/control side | |
Connection | terminals 1+, 3- (terminals 1+, 2 for test loop) | |
Internal resistor | approx. 275 Ω | |
Current | ≤ 20.4 mA | |
Voltage | ≥ 13.5 V | |
Open loop voltage | > 16 V | |
Voltage | 1-signal: > 13.5 V | |
Current | 1-signal: 20.4 A 0-signal: 4.2 mA |
|
Load | max. 650 Ω | |
Response time | < 40 ms input to output | |
Line fault detection | short circuit voltage < 1 V , open circuit voltage > 16 V | |
Output II | ||
Connection | terminal 7: source (-) or sink (+), terminal 8: source (+), terminal 9: sink (-) | |
Current | 11 mA (source or sink mode) | |
Voltage | 9 ... 30 V sink mode from external supply | |
Load | max. 650 Ω , source mode , for HART ≥ 230 Ω | |
Communication | pass-through of HART signal between input II and output | |
Galvanic isolation | ||
Field circuit/control circuit | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | functional insulation, rated insulation voltage 50 Veff | |
Output II/power supply | functional insulation, rated insulation voltage 50 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Height | 119 mm | |
Width | 20 mm | |
Depth | 115 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210101 |
ECLASS 12.0 | 27210190 |
ECLASS 11.0 | 27210190 |
ECLASS 10.0.1 | 27210190 |
ECLASS 9.0 | 27210190 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121008 |
This signal conditioner provides galvanic isolation between field circuits and control circuits.
The device can be used in emergency shutdown applications with HART positioners.
Via the logic input the positioner is energized or de-energized (emergency shutdown).
Independent of the status, a second input enables HART communication with the positioner. With this the asset management system can request for example diagnostic information or can initiate a partial stroke test.
The HART communication also works with de-energized positioner.
If the device is operated via Power Rail, additionally a collective error message is available.
Literature | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation Stage | ENG | 566 KB | |
Application Report - Generating Electricity in Coal-Fired Power Plants | ENG | 412 KB | |
Application Report - Sand Trap and Preliminary Sedimentation Stage | ENG | 448 KB | |
Application Report - Screening Systems in Sewage Treatment Plants | ENG | 577 KB |
Safety and Security Documentation | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction manual | ENG | 41 KB | |
Safety Manual | ENG | 597 KB | |
Manuals | |||
System Manual | ENG | 3694 KB |
CAD | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 3123 KB |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 1308 KB |
Certificates | Sertifika No. | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|---|
exida Functional Safety Assessment | P+F 0905-35R1-C R015 V1R0 | ALL | 599 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-7214_TUR | TUR | 219 KB | |
UK Declaration of Conformity (P+F) | TDOC-7231_ENG | ENG | 192 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|