Fabrika Otomasyonu
Proses Otomasyonu

Signal Converter with Trip Value KFU8-USC-1.D

KFU8-USC-1.D
  • 1-channel signal conditioner
  • Universal usage at different power supplies
  • Scaleable current or voltage input
  • Current or voltage output
  • Relay contact output
  • Configurable by keypad
  • Line fault detection (LFD)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Tam veri sayfasını PDF olarak indirin:


Veri sayfası alıntısı: Teknik veriler  KFU8-USC-1.D

General specifications
Signal typeAnalog input
Supply
Connectionterminals 14, 15
Rated voltage20 ... 90 V DC / 48 ... 253 V AC
Rated current≤ 80 mA DC / ≤ 45 mA AC
Power consumption≤ 1.6 W / ≤ 2.6 VA
Input
Connection sidefield side
Connectionterminals 1+, 3- : mV, V ; terminals 2+, 3- : mA
Input resistancevoltage: 1 MΩ , current: max. 100 Ω
Limit30 V
Current0 ... 20 mA
Voltage0 ... 10 V / 0 ... 60 mV
Resolution15 Bit
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12
output II: terminals 7-, 8+, 9-
Output Isignal, relay
Contact loading250 V AC/2 A/cos φ 0.7; 40 V DC/2 A
Mechanical life2 x 107 switching cycles
Energized/De-energized delayapprox. 10 ms / approx. 10 ms
Output IIanalog
Loadcurrent: max. 550 Ω , voltage: min. 1 kΩ
Analog voltage output0/1 ... 5 V , 0/2 ... 10 V
Analog current output0/4 ... 20 mA
Transfer characteristics
Deviation0.1 % of full-scale value
Resolution/accuracycurrent: 1 µA/20 µA
voltage: 0.5 mV/10 mV
mV: 3 µV/60 µV
Influence of ambient temperature0.003 %/K (30 ppm)
Reaction time≥ 150 ms/≤ 300 ms
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsdisplay
Control elementsControl panel
Configurationvia operating buttons
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210107
ECLASS 12.027210107
ECLASS 11.027210107
ECLASS 10.0.127210107
ECLASS 9.027210107
ECLASS 8.027210107
ECLASS 5.127210107
ETIM 9.0EC002475
ETIM 8.0EC002475
ETIM 7.0EC002475
ETIM 6.0EC002475
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFU8-USC-1.D

Function

This signal conditioner is suitable for the connection of current and voltage signals and provides isolation for nonintrinsically safe applications.

The input ranges include 0 mA ... 20 mA, 0 V... 10 V or 0 mV... 60 mV. Subranges from the input ranges are selectable.

The output measuring signals are 0/4 mA ... 20 mA, 0/2 V... 10 V or 0/1 V... 5 V.

The output relay serves as trip value contact.

On the display the measured value can be indicated in various physical units.

The unit is easily programmed by the use of a keypad located on the front of the unit.

For additional information, refer to the manual and www.pepperl-fuchs.com.

Informative Literature: KFU8-USC-1.D

Dil Seçeneği:
LiteratureDilDosya TipiDosya Boyutu
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB

Product Documentation: KFU8-USC-1.D

Dil Seçeneği:
Safety and Security DocumentationDilDosya TipiDosya Boyutu
Instruction manualENGPDF41 KB
Manuals
Manual KF**-USC-1.DENGPDF395 KB
System ManualENGPDF3694 KB

Design / Simulation: KFU8-USC-1.D

Dil Seçeneği:
CADDilDosya TipiDosya Boyutu
CAD 3-D / CAD 3-DALLSTP3123 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ52 KB

Approvals: KFU8-USC-1.D

Dil Seçeneği:
Declaration of ConformitySertifika No.DilDosya TipiDosya Boyutu
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2364AALLPDF100 KB

İlişkili Ürünler: KFU8-USC-1.D

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of field and control signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.