Fabrika Otomasyonu
Proses Otomasyonu

HART Termination Board FI-PFH-NS0137-R

FI-PFH-NS0137-R
  • Connection board for K-System HART Multiplexer
  • 16-channel
  • Interface for series connection or parallel connection
  • Integrated, switchable 220 Ω resistor
  • Connection via screw terminals

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Tam veri sayfasını PDF olarak indirin:


Veri sayfası alıntısı: Teknik veriler  FI-PFH-NS0137-R

HART signal channels (non-intrinsically safe)
Load resistor220 Ω , switchable on
Interface
Typemultiplexer connection : IDC plug, 26-pin
Signal lines
Rated currentmax. 30 mA per channel
Indicators/settings
Control elementsDIP switch
DIP switchselection of operating mode:
- ON: without load resistor
- OFF: with load resistor
Factory settingDIP switches S1 and S2: ON
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature0 ... 50 °C (32 ... 122 °F)
Storage temperature-15 ... 50 °C (5 ... 122 °F)
Relative humidity≤ 93 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Mechanical specifications
Degree of protectionIP20
Connection
Field sidescrew terminals , green
Control sidescrew terminals , green
HART : 1 x IDC plug, 26-pin
Core cross section0.25 ... 1.5 mm2 (24 ... 16 AWG)
Material
HousingPVC
Massapprox. 210 g
Dimensions110 x 125 x 61 mm (4.3 x 4.9 x 2.4 inch) (W x H x D)
Height125 mm
Width110 mm
Depth61 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificatePF 11 CERT 1930 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-15:2010
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210190
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127242690
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: FI-PFH-NS0137-R

Function

This HART termination board has 16 terminal blocks to connect up to 16 HART field devices.

It has an integrated, switchable 220  load resistor and an integrated ground capacitor. It also has terminal blocks for the 4 mA ... 20 mA signal to the DCS/ PLC.

A 26-pin flat cable K-HM26 is used for connection of each HART Multiplexers KFD*-HM*-16 to the termination board.

Other termination boards are available. Contact Pepperl+Fuchs for details.

Product Documentation: FI-PFH-NS0137-R

Dil Seçeneği:
ManualsDilDosya TipiDosya Boyutu
Manual KFD*-HM*-16ENGPDF8323 KB

Approvals: FI-PFH-NS0137-R

Dil Seçeneği:
CertificatesSertifika No.DilDosya TipiDosya Boyutu
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3PF11CERT1930 XALLPDF193 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-1070DALLPDF107 KB

İlişkili Ürünler: FI-PFH-NS0137-R

Matching System Components
16-channel, No external power required, HART field device input (revision 5 to 7), Used with HART MUX primary module KFD2-HMM-16, Up to SIL 3 acc. to IEC/EN 61508pa
16-channel, 24 V DC supply (Power Rail), HART field device input (revision 5 to 7), Up to 15 KFD0-HMS-16 HART MUX secondary modules can be connected, Up to SIL 3 acc. to IEC/EN 61508pa
Accessories
K-System accessory, Connection cable for KF*-HM*-16 to Termination Board, 26-pin ribbon cablepa
K-System accessory, Connection cable for KF*-HM*-16 to Termination Board, 26-pin ribbon cablepa
K-System accessory, Connection cable for KFD2-HMM-16 to up to 15 KFD0-HMS-16, 14-pin ribbon cablepa