Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Tam veri sayfasını PDF olarak indirin:
Ürün Açıklaması |
---|
HART MUX Primary Module |
Functional safety related parameters | ||
---|---|---|
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 17+, 18- | |
Rated voltage | 20 ... 32 V DC typical at 100 mA | |
Power consumption | max. 3 W | |
HART signal channels (non-intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for primary module/secondary module connection between KFD2-HMM-16 and KFD0-HMS-16 |
|
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) | |
Output voltage | ≥ 400 mV ss (with the terminator resistance specified above) | |
Output resistance | 100 Ω or smaller, capacitive coupling | |
Input impedance | according to HART specification | |
Input voltage range | 0.08 ... 4 V ss ; typ. ± 5.2 V as local reference | |
Interface | ||
Transfer rate | 9600, 19200, or 38400 Bit/s (selectable with DIL switch (2 and 3) by the user) | |
Type | RS-485 , 2-wire multidrop | |
Address selection | One of 31 possible addresses selectable per DIL switch (4 ... 8) | |
Indicators/settings | ||
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 250 g | |
Dimensions | 40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) (W x H x D) , housing type C1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 07 CERT 1143 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210190 |
ECLASS 12.0 | 27210190 |
ECLASS 11.0 | 27210190 |
ECLASS 10.0.1 | 27210190 |
ECLASS 9.0 | 27210190 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC001601 |
ETIM 8.0 | EC001601 |
ETIM 7.0 | EC001601 |
ETIM 6.0 | EC001601 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 39121008 |
The HART MUX primary module operates up to 256 analog field devices. The built-in secondary module in the primary module operates the first 16 field devices. If more than 16 field devices are required, up to 15 additional HART MUX secondary modules KFD0-HMS-16 can be connected.
The secondary modules are connected to the primary module with a 14-pin flat cable. The connector for the ribbon cable is found on the same housing side as the connectors for the interface and the power supply.
The analog signals are separately linked via a 26-pin flat cable to each secondary module. Sixteen leads are reserved for the HART signal of the analog measurement circuits. The remaining 10 leads are assigned to ground.
The primary module is designed with removable terminals and can be connected to the Power Rail.
Literature | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation Stage | ENG | 566 KB | |
Application Report - Generating Electricity in Coal-Fired Power Plants | ENG | 412 KB | |
Application Report - Sand Trap and Preliminary Sedimentation Stage | ENG | 448 KB | |
Application Report - Screening Systems in Sewage Treatment Plants | ENG | 577 KB |
Safety and Security Documentation | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction manual | ENG | 47 KB | |
Manuals | |||
Manual KFD*-HM*-16 | ENG | 8323 KB |
CAD | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 186 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 212 KB |
Certificates | Sertifika No. | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|---|
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3 | PF 07 CERT 1143 X | ALL | 209 KB | |
exida Functional Safety Assessment | P+F 02/4-11 R006 | ALL | 348 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0777D | ALL | 1040 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-5294A | ALL | 1037 KB |
Device Description Files/Drivers | Sürüm Bilgileri | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
DTM Collection HART-Multiplexer / DTM Collection HART-Multiplexer | 2.0.1.208 | ZIP | 13306 KB |
Software Tools | |||
PACTware 4.1 SP6 / PACTware 4.1 SP6 | 4.1.0.53 | ZIP | 43327 KB |
PACTware 5.0 / PACTware 5.0 | 5.0.5.31 | ZIP | 44203 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
Matching System Components | ||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|