Fabrika Otomasyonu
Proses Otomasyonu

FieldBarrier Junction Box, Polyester (GRP) F.FB1.P14.A**.1.*.***.***.****

F.FB1.P14.A**.1.*.***.***.****
  • 8, 10, 12 outputs Ex ia
  • Impact resistance enclosure, IP66
  • Configurable cable entries for trunk and spurs
  • Packaged certified solution
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Installation in Zone 1

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Tam veri sayfasını PDF olarak indirin:


Veri sayfası alıntısı: Teknik veriler  F.FB1.P14.A**.1.*.***.***.****

General specifications
Design / MountingOutside installation
Installed componentsFieldBarrier R4D0-FB-IA*
For technical data on installed electronic component see data sheet.
Conformity
Degree of protectionEN 60529
Impact resistanceEN 60079-0
Ambient conditions
Ambient temperature-30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
Impact resistance7J
Mechanical specifications
Enclosure coverdetachable cover with retaining screws
Degree of protectionIP66
Cable entrycable gland and stopping plug options see separate table
Material
Housingpolyester , impact resistant, glass fiber reinforced
Grounding platebrass
Surfaceblack (RAL 9011)
Surface resistance< 109 Ω
Water absorption< 6 %
Sealsilicone , one-piece
Material thicknessgrounding plate: 3 mm
Dimensions(W x H x D)
405 x 400 x 200 mm
Mountingthru-holes Ø6.5 mm
Groundinggrounding bolt M6 , brass
Data for application in connection with hazardous areas
EU-type examination certificatePTB 07 ATEX 1061 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II 2(1)G Ex db eb ib mb [ia Ga] IIC T4 Gb
Ex-Hexagon II 2(1)D Ex tb [ia Da] IIIC T135°C Db
Note: The marking is based on the maximum value and can be reduced depending on the selected options accordingly.
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-1:2014 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-18:2009 , EN 60079-31:2014
International approvals
IECEx approvalIECEx PTB 07.0036 X , suitable Junction Box on request
INMETRO approvalTÜV 13.1143
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242605
ECLASS 12.027242605
ECLASS 11.027242605
ECLASS 10.0.127242605
ECLASS 9.027242605
ECLASS 8.027242605
ECLASS 5.127242605
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: F.FB1.P14.A**.1.*.***.***.****

Function

This Junction Box is a device coupler with a diagnostic-enabled FieldConnex ® FieldBarrier for Zone 1. Devices can be located in Zone 0.

Glass fiber-reinforced polyester provides corrosion resistance and is light weight. The surface resistance avoids electrostatic charge.

Trunk and spur entries can be selected individually from a range of cable glands and stopping plugs. A breather is included by default. Tag plate, grounding bar, surge protection for trunk and spurs are available as options. For the spurs, surge protection is available with integrated diagnostics.

This junction box is available pre-wired, with all accessories, for fast ordering, delivery, site installation, and commissioning.

Informative Literature: F.FB1.P14.A**.1.*.***.***.****

Dil Seçeneği:
LiteratureDilDosya TipiDosya Boyutu
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F.FB1.P14.A**.1.*.***.***.****

Dil Seçeneği:
Safety and Security DocumentationDilDosya TipiDosya Boyutu
Instruction manualENGPDF140 KB
Manuals
ManualENGPDF915 KB

Approvals: F.FB1.P14.A**.1.*.***.***.****

Dil Seçeneği:
CertificatesSertifika No.DilDosya TipiDosya Boyutu
Brasil TUV Rheinland BrazilTÜV 13.1143ALLPDF1259 KB
Europe PTB ATEX Category 2 G ATEX Category 2 DPTB 07 ATEX 1061 XALLPDF500 KB
Worldwide PTB IECEx Certificate of Conformity CertificateIECEx PTB 07.0036XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3152CALLPDF135 KB

İlişkili Ürünler: F.FB1.P14.A**.1.*.***.***.****

Matching System Components
FieldConnex® Fieldbus, Fieldbus barrier, module for DIN rail mounting, 8 ... 12 outputs Ex ia IIC, FISCO and Entity, Advanced fault isolation and diagnostics at the spur, FieldBarrier in Zone 1/Div. 2, Instruments in Zone 0...1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Device coupler location: Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

Kararlardan planlamaya, kuruluma ve devreye almaya, işletme ve bakıma kadar: Fieldbus altyapınızdan en iyi şekilde nasıl yararlanabileceğinizi keşfedin…