Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Tam veri sayfasını PDF olarak indirin:
General specifications | ||
---|---|---|
Number of protected signal lines | 2 | |
Topology | non-grounded | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Electrical specifications | ||
Connection | via base module | |
Leakage current | < 30 µA bei Uc , line-line < 10 nA bei Uc , line-earth |
|
Nominal voltage | 24 V | |
Maximum continuous operating voltage | 25.4 V AC and 36 V DC | |
Nominal load current | 0.5 A at 80 °C (176 °F) | |
Series resistance | 1 Ω per line | |
Impulse discharge current (10/350 µs) | 1.5 kA per line | |
Nominal discharge current (8/20 µs) | 5 kA per line | |
Max. surge current (8/20 µs) | 20 kA | |
Total discharge current (8/20 µs) | 10 kA | |
Voltage protection level | max. 65 V line-line for nominal discharge current In max. 1100 V line-earth for nominal discharge current In |
|
Impulse reset time | < 30 ms | |
Cut-off frequency | 3.5 MHz , line-line | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) |
|
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Functional safety | IEC/EN 61508:2010 | |
Surge protective devices for low voltage | EN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012 |
|
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) For usage in hazardous area observe the EU-type examination certificate. |
|
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Relative humidity | max. 95 % , without condensation | |
Corrosion resistance | acc. to ISA-S71.04, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | via base module | |
Material | ||
Housing | Polyamide PA 6.6 | |
Mass | approx. 14 g | |
Dimensions | 6 x 45 x 54 mm (0.24 x 1.77 x 2.15 inch) (W x H x D) | |
Height | 45 mm | |
Width | 6 mm | |
Depth | 54 mm | |
Mounting | pluggable in base module for mounting on 35 mm DIN mounting rail | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | TÜV 22 ATEX 8880 X | |
Marking | II (1)2G Ex ia [ia Ga] IIC T6...T4 Gb II 2G Ex ib IIC T6...T4 Gb II (1)D [Ex ia Da] IIIC |
|
Temperature class | T6 for ambient temperature ≤ 50 °C T5 for ambient temperature ≤ 70 °C T4 for ambient temperature ≤ 80 °C |
|
Voltage | 30 V | |
Current | 500 mA , restrictions see certificate | |
Power | 5.32 W | |
Internal capacitance | negligible | |
Internal inductance | negligible | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2018 , EN IEC 60079-7:2015+A1:2018 , EN 60079-11:2012 | |
International approvals | ||
IECEx approval | ||
IECEx certificate | IECEx TUR 22.0050X | |
IECEx marking | Ex ia [ia Ga] IIC T6...T4 Gb Ex ib IIC T6...T4 Gb [Ex ia Da] IIIC |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27171202 |
ECLASS 12.0 | 27171202 |
ECLASS 11.0 | 27130805 |
ECLASS 10.0.1 | 27130805 |
ECLASS 9.0 | 27130805 |
ECLASS 8.0 | 27130805 |
ECLASS 5.1 | 27130801 |
ETIM 9.0 | EC000941 |
ETIM 8.0 | EC000941 |
ETIM 7.0 | EC000941 |
ETIM 6.0 | EC000941 |
ETIM 5.0 | EC000941 |
UNSPSC 12.1 | 39121610 |
The protection module limits induced transients of different causes, e. g. lightning or switching operations. The limitation is achieved by diverting the current to earth and limiting the signal circuit voltage during the duration of the overvoltage pulse.
The device is a spare part for the corresponding 2-part surge protection barrier. The device is not to be used as a stand-alone device.
The device is HART transparent.
The device has a status indication at the front.
The device can be replaced without tools by locking levers.
Brief Instructions | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 5366 KB | |
Safety and Security Documentation | |||
Functional Safety Manual | ENG | 1990 KB |
CAD | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 1283 KB |
CAE | |||
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 700 KB |
Certificates | Sertifika No. | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|---|
China CNEX CCC Ex Certificate | 2023312304001608 (DEHN SE) | ALL | 589 KB | |
EU ATEX Category 2 G EU-Type Exam. Certificate ATEX Category (1) D ATEX Category 2 (1) | ATEX TÜV 22 ATEX 8880 X | ALL | 196 KB | |
TUV Rheinland IECEx Certificate of Conformity | IECEx TUR 22.0050X | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-7115_TUR | TUR | 186 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|