Ürün Açıklaması |
---|
Direct Monitor - System with Enclosure |
General specifications | ||
---|---|---|
Type | Direct Monitor | |
Supply | ||
Power consumption | ||
AC | A: 115/230 V a.c. (100 ... 240 V a.c.), max. 0.4 A For connections designation refer to the Power Supply PS1000-A6-24.5 manual. |
|
DC | D: 20 ... 28 V d.c. / 1.5 A (SELV/PELV or class 2) For connections designation refer to the VisuNet FLX Panel Mount manual. |
|
Indicators/operating means | ||
Display | ||
Type | Liquid Crystal Display (LCD) with LED backlight | |
Screen diagonal | 54.61 cm (21,5 '') | |
Resolution | 1920 x 1080 pixels (Full HD) Aspect ratio 16:9 |
|
Color depth | 24 bit (16.7 M) color | |
Contrast | Typically 22GT: 1000:1 22FC: 5000:1 |
|
Brightness | Configurable display options: 22GT: 250 cd/m2 22FC: 300 cd/m2 |
|
Reading angle | 22GT: 178 ° in all directions 22FC: 170 ° horizontal, 160 ° vertical |
|
Life span | 22GT: back lamp life: 30.000 hrs typical half life, at 25 °C (77 °F) 22FC: back lamp life: 50.000 hrs typical half life, at 25 °C (77 °F) |
|
Input devices | ||
Touch screen | 10-finger multi-touch, glove-friendly Configurable display options: 22GT: Capacitive touch, no optical bonding 22FC: Capacitive touch, optical bonding |
|
Keyboard | Optional: Foil keyboard with different pointing device options available (see EXTA4 datasheet) | |
Interface | ||
Interface type | 1x Power input w/ 3 pin terminal block 1x HDMI 1x DVI-I 1x VGA 1x USB 1x 3,5mm audio jack (Line-out) 1x OSD Menu w/ power button |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (ind. Locations) EN 61000-6-4:2007+A1:2011 |
|
Explosion protection | ||
Directive 2014/34/EU | EN IEC 60079-0:2018 EN IEC 60079-7:2015/A1:2018 EN 60079-31:2014 |
|
RoHS | ||
Directive 2011/65/EU (RoHS) | EN IEC 63000:2018 | |
Ambient conditions | ||
Operating temperature | 0 ... 40 °C (32 ... 104 °F) |
|
Storage temperature | -20 ... 65 °C (-4 ... 149 °F) | |
Relative humidity | max. relative humidity 93% at 40°C (non-condensing) according to EN60068-2-78 | |
Climatic conditions | Passive cooling, no rotating parts. | |
Altitude | Operating altitude max. 2000 m | |
Shock resistance | 18 shocks 15 g, 11 ms all axis, IEC 60068-2-27 | |
Vibration resistance | 10 ... 150 Hz, +/- 0.075 mm, 1g, 10 cycles per axis according to EN60068-2-6 | |
Mechanical specifications | ||
Degree of protection | IP66/Type 4X | |
Material | Housing: Stainless steel AISI304 (1.4301) Surface finish: Bead blasted, typical surface roughness 0.8 µm |
|
Installation | System with enclosure | |
Mass | approx. 16 kg approx. 18 kg with AC Power Supply |
|
Dimensions | 577 mm x 466 mm x 233 mm | |
International approvals | ||
UL approval | ||
Approved for | UL OrdLoc UL approval E223772 UL61010-1 Ed.3 UL 61010-2-201 Ed2 CAN/CSA C22.2 No 61010-1-12 CAN/CSA C22.2 No 61010-2-201 UL approval E492874 Non-Incendive circuits for CL I, DIV 2, GP A-D CL II, DIV 2, GP F, G CL III Non-Incendive circuits for CL I, ZN 2, IIC CL II, ZN 22, IIIB CL III, ZN 22, IIIA Install per drawing 116-0478 Mounting in CL I, DIV 2, GP A-D, T4 CL II, DIV 2, GP F, G, T4 CL III Mounting in CL I, ZN 2, IIC, T4 CL II, ZN 22, IIIB, T85°C CL III, ZN 22, IIIA, T85°C |
|
ATEX approval | ||
ATEX certificate | UL 22 ATEX 2481X | |
ATEX marking | II 3 G Ex ec [ic] IIC T4 Gc II 3 D Ex tc IIIC T85°C Dc |
|
IECEx approval | ||
IECEx certificate | IECEx ULD 22.0019X | |
IECEx marking | Ex ec IIC T4 Gc Ex tc IIIC T85°C Dc |
|
IECEx standard | IEC 60079-0:2017 Ed 7.0 IEC 60079-7:2017 Ed 5.1 IEC 60079-31:2013 Ed. 2 |
|
CCC approval | ||
CCC certificate | 2023322309005595 | |
CCC marking | Ex ec IIC T4 Gc Ex tc IIIC T85°C Dc |
|
CCC standard | GB 3836.1-2021 GB/T 3836.3-2021 GB/T 3836.31-2021 |
System | Classcode |
---|---|
ECLASS 13.0 | 27330190 |
ECLASS 12.0 | 27330190 |
ECLASS 11.0 | 27330190 |
ECLASS 10.0.1 | 27330190 |
ECLASS 9.0 | 27330190 |
ECLASS 8.0 | 27330190 |
ECLASS 5.1 | 27242301 |
ETIM 9.0 | EC002504 |
ETIM 8.0 | EC002504 |
ETIM 7.0 | EC002504 |
ETIM 6.0 | EC002504 |
ETIM 5.0 | EC001412 |
UNSPSC 12.1 | 39121106 |
The VisuNet FLX Systems are designed for Zone 2/22 (Div.2) and non-Ex applications. The different mounting and configuring options lead to the highest application flexibility. Due to a fully modular design, the new platform, which is geared to the needs of the (petro-) chemical and pharmaceutical industries, the HMIs can be configured to fit exactly and enables simple and fast adjustments in the field. With the modern, compact design less installation space is required. The low weight allows a cost effective and easy installation.
Safety and Security Documentation | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction manual | ENG | 249 KB | |
Manuals | |||
Manual - VisuNet FLX System | ENG | 32436 KB |
Certificates | Sertifika No. | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|---|
ATEX | UL 22 ATEX 2481X | ALL | 592 KB | |
China SITIIAS CCC Ex Certificate | 2023322309005595 (Mannheim) | ALL | 1297 KB | |
IECEx Certificate of Conformity | IECEx ULD 22.0019X | ALL | LINK | --- |
UL Hazardous Location | E492874 | ALL | 194 KB | |
UL Ordinary Location | E223772 | ALL | 194 KB | |
Declaration of Conformity | ||||
EU-Declaration of Conformity VisuNet FLX System DC (Non-Ex) / EU-Konformitätserkärung VisuNet FLX System DC (Non-Ex) | DOC-4983B | ALL | 211 KB | |
EU-Declaration of conformity ATEX RM-320S-L / PC-320S-L / DM-320S-L / EU-Konformitätserklärung ATEX RM-320S-L / PC-320S-L / DM-320S-L | DOC-5836C | ALL | 215 KB | |
EU-Declaration of conformity VisuNet FLX System AC (Non-Ex) / EU-Konformitätserklärung VisuNet FLX System AC (Non-Ex) | DOC-5300B | ALL | 211 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|