Temperature control unit with LED display KT-LED-96-2R-24VDC

KT-LED-96-2R-24VDC
  • Galvanic isolation
  • Polarity reversal protected
  • Degree of protection IP65 (front only)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KT-LED-96-2R-24VDC

Product Description
Temperature control unit with LED display and 24 VDC supply voltage
General specifications
Data storage106 storage cycles or 10 years, EEPROM
Programmingkeypad-driven menu
Indicators/operating means
Type5-digit 7-segment LED display, red
Display valuedigit height 14.2 mm
Display interval-19999 ... 99999
with suppression of leading zeros
Decimal point0 to max 1 fractional digit
Resetmanually or external
Electrical specifications
Fusing250 mA/T
Operating voltage10 ... 30 V DC galvanically isolated
Power consumptionmax. 2 W
Input 1
Input typemeasurement for thermoelements B, E, J, K, N, R, S, T
Resolution0.1 °C (0.1 °F)
Compensation (reference junction CJC)internal or external (programmable)
Input 2
Input typeMeasurement input for resistance thermometer type Pt100, Pt1000
Resolution0.1 °C (0.1 °F)
Connection2-, 3- and 4-wire connection technology, programmable
Current800 µA at Pt100
80 µA at Pt1000
Input 3
Input typeMeasurement input for resistance measurement
Resistor0 ... 400 Ω
0 ... 4000 Ω
Resolution14 Bit
Connection2-, 3- and 4-wire connection technology, programmable
Current800 µA at 400 Ω
80 µA at 4000 Ω
Input 4
Input typeMillivolt measurement input with automatic zero adjustment
Voltage range0 ... 100 mV DC
-100 ... 100 mV DC
Resolution14 Bit
Input resistancemin. 2 MΩ
Measuring frequencyapprox. 1 measurement per sec.
Input 5
Input typeDigital inputs,
Input MPI: Display hold or reset limit value latch
Input KEY: Keyboard lock
Signal voltage
High4 ... 30 V DC
Low0 ... 2 V DC
Minimum pulse durationmin. 5 ms
Output 1
Output type2 limit value outputs, relay with floating changeover contact
Switching voltage250 V AC / 300 V DC
Switching currentmax. 3 A AC/DC
min. 30 mA DC
Switch power50 W / 2000 VA
Output 2
Output typeAuxiliary power output for signal converter/measurement sensor,
galvanically isolated
Output voltage10 V DC ± 3 %, 30 mA,
Compliance with standards and directives
Directive conformity
EMC Directive 2004/108/ECEN 61000-6-2:2005
Standard conformity
Emitted interferenceDIN EN 55011:2009, Class B
Ambient conditions
Ambient temperature-20 ... 65 °C (-4 ... 149 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity≤ 75 % (noncondensing)
Mechanical specifications
Degree of protectionIP65 (front)
Massapprox. 212 g
Dimensions96 mm x 48 mm x 90.7 mm

Classifications

SystemClasscode
ECLASS 13.027210301
ECLASS 12.027210301
ECLASS 11.027210301
ECLASS 10.0.127210301
ECLASS 9.027210301