Product Description |
---|
G10 ultra compact module, 2 inputs, 2 x M12 socket |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.0 | |
Profile | S-0.A.2 | |
IO code | 0 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 2 | |
UL File Number | E223772 "For use in NFPA 79 Applications only" | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs |
|
LED AS-i | AS-Interface voltage; LED green | |
LED IN | switching state (input); 2 LED yellow | |
Electrical specifications | ||
Rated operating voltage | 18.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 40 mA (without sensors) / max. 120 mA | |
Protection class | III | |
Input | ||
Number/Type | 2 inputs for 2- or 3-wire sensors (PNP), DC | |
Supply | from AS-Interface | |
Voltage | 21 ... 31 V | |
Current loading capacity | 75 mA at TB ≤ 40 °C (104 °F) 60 mA at TB ≤ 75 °C (167 °F) overload and short-circuit resistant |
|
Input current | ≤ 9 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | ≤ 3 mA | |
1 (attenuated) | ≥ 5 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2:2007 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Approvals and certificates | ||
UL approval | cULus Listed, Type 1 enclosure | |
Maximum permissible ambient temperature | max. 65 °C (max. 149 °F) | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
|
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Mechanical specifications | ||
Degree of protection | housing: IP67 IP67 / IP68 / IP69K with flat cable VAZ-FK-S-* M12 socket: IP67/IP68/IP69K |
|
Connection | AS-Interface: AS-Interface flat cable Inputs & matching connector: X1 & X2, M12 plug, 4-pin, A-coded, in accordance with IEC 61076-2-101:2012 |
|
Material | ||
Contacts | CuSn / Au | |
Housing | PBT PC | |
Body | PUR, black | |
Cable | PUR | |
Mounting screw | Stainless steel 1.4305 / AISI 303 | |
Cable | ||
Sheath diameter | ∅4,3 mm | |
Color | black | |
Cores | 4 x 0.34 mm2 | |
Length | 1 m | |
Mass | 100 g | |
Tightening torque, fastening screws | 1.65 Nm | |
Tightening torque, cable gland | 0.4 Nm | |
Dimensions | ||
Height | 21.5 mm | |
Width | 27.7 mm | |
Length | 40.5 mm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
The AS-Interface G10 ultra-compact module is suitable for the remote connection of sensors within very limited space. The one-piece enclosure has the protection degree IP68/IP69K.
The AS-Interface flat cable is contacted via pointy, gold-plated contact pins. The exact location of the pins on the lead is ensured by the swivel mechanism. Sensors are connected to the module via M12 sockets.
Multiple LEDs indicate the current status of the AS-Interface strand and the inputs and are used for diagnosis.
The ultra-compact module is powered from the AS-Interface strand.
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 185 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 137 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Canada, USA | CoC 20171220-E223772 RptRef E223772-20130501 | ALL | 442 KB | |
EU Ecolab Material Resistance | ECOLAB | ALL | 1096 KB | |
Worldwide AS-International Association AS-Interface | 92402 | ALL | 383 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2374E | ALL | 118 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability
The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.