LB6101H Relay output
Principaux avantages en un coup d'œil
- 2-channel
- Simulation mode for service operations (forcing)
- Mounting in Zone 2, Class I/Div.2 or in the safe area
- Permanently self-monitoring
- Output with watchdog
- Module can be exchanged under voltage
Afficher plus
Type préféré



Remarque
Tous les documents relatifs aux produits, tels que les certificats, les déclarations de conformité, etc., qui ont été émis avant la conversion sous le nom de Pepperl+Fuchs GmbH ou Pepperl+Fuchs AG, s'appliquent également à Pepperl+Fuchs SE.
DE
- DE
- EN
Fiche techniqueFonctionClassificationInformative LiteratureProduct DocumentationDesign / SimulationAgrémentsProduits connexes
Données techniques relatives à LB6101H
Occupied slots | 1 |
Connection | backplane bus | |
Rated voltage | Ur | 12 V DC , only in connection with the power supplies LB9*** |
Power dissipation | 0.65 W | |
Power consumption | 0.65 W |
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit |
Connection | channel I: 1-2 NC, 3; channel II: 4-5 NC, 6 | |||||||||||||
Minimum load | 1 V , 1 mA | |||||||||||||
Relay | ||||||||||||||
| ||||||||||||||
Response time | 20 ms (depending on bus cycle time) | |||||||||||||
Contact Material | AgPd gold plated | |||||||||||||
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
Number of channels | 2 | |||||||||||||||||||
Field device interface | ||||||||||||||||||||
| ||||||||||||||||||||
Connection | channel I: 1-2 NC, 3; channel II: 4-5 NC, 6 | |||||||||||||||||||
Relay | ||||||||||||||||||||
| ||||||||||||||||||||
Response time | 20 ms (depending on bus cycle time) | |||||||||||||||||||
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
LED indication | Power LED (P) green: supply Status LED (1, 2) yellow: signal (per channel) | |
Coding | optional mechanical coding via front socket |
Electromagnetic compatibility | |||||
| |||||
Low voltage | |||||
|
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Environmental test | EN 60068-2-14 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Damaging gas | EN 60068-2-42 | |
Relative humidity | EN 60068-2-78 |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) , 70 °C (non-Ex) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Altitude | max. 2000 m | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Degree of protection | IP20 when mounted on backplane | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 90 g | |
Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) |
Certificate | PF 08 CERT 1234 X | ||||
| |||||
Galvanic isolation | |||||
| |||||
Directive conformity | |||||
|
ATEX approval | PF 08 CERT 1234 X | |||||||
UL approval | E106378 | |||||||
IECEx approval | ||||||||
|
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |