Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Descargue la hoja de datos completa en PDF:
Descripción del producto |
---|
Safety Monitor, 16 decentralized output circuits |
General specifications | ||
---|---|---|
AS-Interface specification | V3.0 | |
PLC-Functionality | none | |
Duplicate address detection | from AS-Interface slaves | |
Earth fault detection | integrated | |
EMC monitoring | integrated | |
Diagnostics function | Extended function via display | |
Switch-on delay | < 10 s | |
Response delay | < 40 ms | |
UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Performance level (PL) | PL e | |
MTTFd | 200 a | |
B10d | 2 E+7 | |
Indicators/operating means | ||
Display | Illuminated graphical LC display for addressing and error messages | |
LED FAULT | Error display; red LED red: Communication error red flashing: release circuit error |
|
LED POWER | voltage ON; LED green | |
LED U AS-i 1 / U AS-i 2 | AS-Interface voltage - circuit 1/circuit 2; green LED | |
LED ready | off: - constantly lit: startup/restart lock active flashing: external test required |
|
LED AUX | ext. auxiliary voltage UAUX ; LED green | |
LED EDM/Start | External device monitoring circuit inputs closed, 4x yellow LEDs | |
LED output circuit | Output circuit closed; 4 x green LEDs | |
Button | 4 | |
Electrical specifications | ||
Insulation voltage | ≥ 500 V | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface; 24 V DC |
|
Rated operating current | ≤ 200 mA from 24 VDC ≤ 45 mA from AS-Interface |
|
Interface | ||
Interface type | RS 232, serial | |
Transfer rate | 19.6 kbaud, no parity, 1 start bit, 1 stop bit, 8 data bits | |
Interface 2 | ||
Interface type | Chip card slot | |
Input | ||
Number/Type | 4 EDM/Start inputs: EDM: Inputs for the external device monitoring circuits Start: start inputs: Static switching current 4 mA at 24 V, dynamic 30 mA at 24 V (T=100 μs) |
|
Output | ||
Safety output | Output circuits 1 and 2: 2 potential-free contacts, max. contact load: 3 ADC-13 at 30 VDC, 3 AAC-15 at 30 VAC Output circuits 3 and 4: 2 PNP transistor outputs max. contact load: 0.5 ADC-13 at 30 VDC |
|
Connection | ||
AS-Interface | spring terminals, removable | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | |
Standard conformity | ||
Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-6-4:2007 | |
Degree of protection | EN 60529:2000 | |
AS-Interface | EN 62026-2:2013 | |
Shock resistance | EN 61131-2:2004 | |
Standards | EN 61000-6-2:2005, EN 61000-6-4:2007 EN 954-1:1996 (up to Kategorie 4), IEC 61508:2001 and EN 62061:2005 (up to SIL3) EN 13849:2008 (PL e) | |
Approvals and certificates | ||
UL approval | An isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
|
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | Stainless steel | |
Mass | 800 g | |
Dimensions | ||
Height | 120 mm | |
Width | 85 mm | |
Length | 89 mm | |
Construction type | Low profile housing , Stainless steel |
System | Classcode |
---|---|
ECLASS 13.0 | 27243101 |
ECLASS 12.0 | 27243101 |
ECLASS 11.0 | 27243101 |
ECLASS 10.0.1 | 27243101 |
ECLASS 9.0 | 27243101 |
ECLASS 8.0 | 27279215 |
ECLASS 5.1 | 27279215 |
ETIM 9.0 | EC001449 |
ETIM 8.0 | EC001449 |
ETIM 7.0 | EC001449 |
ETIM 6.0 | EC001449 |
ETIM 5.0 | EC001449 |
UNSPSC 12.1 | 39121535 |
Product information | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|
Configuring a Safe Input on AS-Interface Safety at Work | ENG | 258 KB | |
Brief Instructions | |||
Installation instructions VAS-4A16L-K31 / Montageanweisung VAS-4A16L-K31 | ALL | 1543 KB | |
Manuals | |||
Manual VAS-2A1L-K31 & VAS-4A16L-K31 | ENG | 5570 KB | |
Replacing the AS-Interface consortial Safety Monitor | ENG | 3164 KB |
CAD | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2685 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Número de Certificado | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|---|
US CA UL | E223772 | ALL | LINK | --- |
Software Tools | Liberar Info | Tipo de archivo | Tamaño |
---|---|---|---|
SISTEMA SLB Library AS-Interface Safety / SISTEMA SLB Library AS-Interface Safety | ZIP | 622 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|