Teknisk support Industrielle sensorer
Kundeservice, eksplosjonsbeskyttelse

Relay Module KFD0-RSH-1.1D.F1

KFD0-RSH-1.1D.F1
  • 1-channel signal conditioner
  • 24 V DC supply (loop powered)
  • Logic input 19 V DC ... 26.5 V DC, non-polarized
  • Relay contact output for de-energized to safe function
  • Test pulse immunity
  • Up to SIL 3 acc. to IEC/EN 61508
  • Up to PL e acc. to EN/ISO 13849

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Last ned komplett datablad som PDF:


Datablad utdrag: Tekniske data for  KFD0-RSH-1.1D.F1

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Systematic capability (SC)SC 3
Performance level (PL)PL e
Supply
Connectionloop powered
Rated voltage19 ... 30 V DC loop powered
Power dissipation< 1.5 W
Power consumption< 1.5 W
Input
Connection sidecontrol side
ConnectionInput terminals 7, 8 ; test input terminals 9, 10, 11, 12
Pulse/Pause ratio150 ms / 150 ms
Test pulse lengthmax. 4 ms from DO card
Test inputsee functional safety manual
Signal level0-signal: -5 ... 5 V
1-signal: 19 ... 26.5 V
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: ≥ 36 mA (minimum load current DO card)
Output
Connection sidefield side
Connectionterminals 4, 5, 6
Contact loading253 V AC/5 A/cos φ 0.7; 30 V DC/5 A resistive load
253 V AC / 1/2 HP
Minimum switch current10 mA / 24 V DC
Energized/De-energized delay150 ms / 150 ms
Mechanical life5 x 106 switching cycles
Fuse rating2.5 A (scope of delivery)
max. 5 AT, recommended maximum utilization of the fuse: 80 %
Transfer characteristics
Switching frequency< 3 Hz
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Machinery Directive
Directive 2006/42/ECEN IEC 62061:2021 , EN/ISO 13849-1:2015
Conformity
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-1:2008 , EN 61326-3-2:2008
Degree of protectionIEC 60529:2013
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Observe the temperature range limited by derating, see section derating.
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 120 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210101
ECLASS 11.027210101
ECLASS 10.0.127210101
ECLASS 9.027210101
ECLASS 8.027210101
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121543

Details: KFD0-RSH-1.1D.F1

Function

This signal conditioner provides the galvanic isolation between field circuits and control circuits.

The device is a relay module that is suitable for safely switching applications of a load circuit. The device isolates load circuits up to 230 V and the 24 V control circuit.

The de-energized to safe (DTS) function is permitted for SIL 3 and PL e applications.

The relays are of diverse design, but have a common effect on the individual switching output.

For testing of the relays, test terminals can be used. The test mode will be indicated by a LED according to NAMUR NE44.

The output is protected against contact welding by a fuse.

Informative Literature: KFD0-RSH-1.1D.F1

Velg språk:
LiteratureSpråkFiltypeFilstørrelse
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB

Product Documentation: KFD0-RSH-1.1D.F1

Velg språk:
Safety and Security DocumentationSpråkFiltypeFilstørrelse
Instruction manualENGPDF136 KB
Functional Safety ManualENGPDF1928 KB
Manuals
System ManualENGPDF3694 KB

Design / Simulation: KFD0-RSH-1.1D.F1

Velg språk:
CADSpråkFiltypeFilstørrelse
CAD 3-D / CAD 3-DALLSTP2510 KB
CAE
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ1171 KB

Approvals: KFD0-RSH-1.1D.F1

Velg språk:
CertificatesSertifikatnummerSpråkFiltypeFilstørrelse
DNV MarineTAA00001WXALLPDF106 KB
Worldwide TUV Rheinland Functional Safety Certificate968/FSP 1255.01/23 ENALLPDF620 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-5026AENGENGPDF169 KB

Relaterte produkter: KFD0-RSH-1.1D.F1

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of field and control signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.

K-System Safety Relays

Pepperl+Fuchs is setting a new level of reliability with newly developed safety relays. With multi-redundant switching contacts, the interface module from the tried-and-tested K-System provides reliable and safety-related activation and deactivation for applications in accordance with IEC61508 up to SIL 3.