Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
Produktbeskrivelse |
---|
AS-Interface enabling switch, 3-layered |
General specifications | ||
---|---|---|
Node type | Safety-Slave | |
AS-Interface specification | V2.1 | |
Required master specification | ≥ V2.0 | |
Switching principle | slow-acting contact element, 3-stage | |
UL File Number | E179102 | |
Functional safety related parameters | ||
Performance level (PL) | PL d | |
B10d | 1 E+5 | |
Electrical specifications | ||
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 45 mA | |
Rated insulation voltage | 50 V | |
Input | ||
Number/Type | 2 safety-related inputs: NO E1 NO E2 |
|
Supply | from AS-Interface | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
AS-Interface | EN 62026-2:2013 | |
Functional safety | DIN EN 954-1, EN ISO 13849-1 (up to PLd) | |
Programming instructions | ||
Profile | S-0.B | |
IO code | 0 | |
ID code | B | |
ID1 code | F | |
ID2 code | E | |
Data bits (function via AS-Interface) | Input | |
D0 | dyn. safety code 1 | |
D1 | dyn. safety code 1 | |
D2 | dyn. safety code 2 | |
D3 | dyn. safety code 2 | |
Ambient conditions | ||
Ambient temperature | -5 ... 50 °C (23 ... 122 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Connection | M12 x 1 connector | |
Material | ||
Housing | Polyamide (PA) | |
Protective cover | Neoprene | |
Mass | approx. 140 g (without conduction) | |
Life span | 105 cycles |
System | Classcode |
---|---|
ECLASS 13.0 | 27371228 |
ECLASS 12.0 | 27371228 |
ECLASS 11.0 | 27371228 |
ECLASS 10.0.1 | 27371228 |
ECLASS 9.0 | 27371228 |
ECLASS 8.0 | 27371228 |
ECLASS 5.1 | 27371228 |
ETIM 9.0 | EC001028 |
ETIM 8.0 | EC001028 |
ETIM 7.0 | EC001028 |
ETIM 6.0 | EC001028 |
ETIM 5.0 | EC001028 |
UNSPSC 12.1 | 39121533 |
The enabling switch, VAA-3E-HH30-J-S-V1, is a 3-stage actuation switch with 2 inputs. NO contacts E1 and E2 are monitored via the inputs. Evaluation takes place via a safety monitor.
Connection is via an M12 plug. The enabling switch is powered via the AS-Interface. The 3-stage slow-action contact element activates the enabling function only in the second stage. The second stage is the center position and has a pressure point. The enabling function is cancelled by releasing the button as well as by pressing it down. Pressing the button down is also referred to as the panic function. When the depressed button is returned to its initial position, the enabling function is no longer activated. The enabling button has NC contacts for the panic function.
Brief Instructions | Språk | Filtype | Filstørrelse |
---|---|---|---|
Instruction Manual VAA-3E-HH30-J-S-V1 / Betriebsanleitung VAA-3E-HH30-J-S-V1 | ALL | 113 KB |
CAD | Språk | Filtype | Filstørrelse |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 400 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
Canada, USA UL | E179102 | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 84301 | ALL | 343 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2390B | ALL | 108 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-7204 | ALL | 106 KB |
Software Tools | Frigivelsesinfo | Filtype | Filstørrelse |
---|---|---|---|
SISTEMA SLB Library AS-Interface Safety / SISTEMA SLB Library AS-Interface Safety | ZIP | 622 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|