Teknisk support Industrielle sensorer
Kundeservice, eksplosjonsbeskyttelse

Zener Barrier SB8002

SB8002
  • 1-channel
  • DC version, positive polarity
  • Max. working voltage 10.6 V
  • Series resistance approx. 18.7 Ω
  • Fuse rating 100 mA
  • DIN rail mountable

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Last ned komplett datablad som PDF:


Datablad utdrag: Tekniske data for  SB8002

General specifications
TypeDC version, positive polarity
Electrical specifications
Series resistanceapprox. 18.7 Ω
Hazardous area connection
Connectionterminals 13, 23
Output voltageUin - 1.4 V at 75 mA
Safe area connection
Connectionterminals 11, 21
Working voltage9 ... 10.6 V
Short-circuit currentmax. 95 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Relative humidity< 95 % (30 d/year), no moisture condensation
Mechanical specifications
Degree of protectionIP20
Connectionscrew connection, max. 2.5 mm2
PA connection, max. 4 mm2
Massapprox. 100 g
Dimensions22.5 x 79 x 85.5 mm (0.88 x 3.11 x 3.36 inch) (W x H x D)
Height79 mm
Width22.5 mm
Depth88.5 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 16 ATEX 181955 X
MarkingEx-Hexagon II (2)G [Ex ib Gb] IIC
Ex-Hexagon II (2)D [Ex ib Db] IIIC
Ex-Hexagon I (M2) [Ex ib Mb] I
Voltage12.4 V
Current95 mA
Power1180 mW (rectangular characteristic curve)
Supply
Maximum safe voltage250 V AC / 125 V DC (Attention! Um is no rated voltage.)
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012
International approvals
IECEx approval
IECEx certificateIECEx TUN 16.0023 X
IECEx marking[Ex ib Gb] IIC
[Ex ib Db] IIIC
[Ex ib Mb] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027211016
ECLASS 12.027211016
ECLASS 11.027211016
ECLASS 10.0.127219001
ECLASS 9.027219001
ECLASS 8.027219001
ECLASS 5.127210702
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC002653
UNSPSC 12.139121018

Details: SB8002

Function

The zener barrier prevents the transfer of unacceptably high energy from the non-hazardous area into the hazardous area.

The zener diodes in the zener barrier are connected in the reverse direction. The breakdown voltage of the diodes is not exceeded in normal operation. If this voltage is exceeded, due to a fault in the non-hazardous area, the fuse will blow. Additionally, the fuse will blow if the current is too high. The zener barrier has a positive polarity, i. e. the anodes of the zener diodes are grounded.

Product Documentation: SB8002

Velg språk:
Brief InstructionsSpråkFiltypeFilstørrelse
Instruction leaflet / BeipackzettelALLPDF257 KB

Approvals: SB8002

Velg språk:
CertificatesSertifikatnummerSpråkFiltypeFilstørrelse
Europe TUV Nord II (2) D II (2) G ATEX Category MTÜV 16 ATEX 181955 XALLPDF285 KB
TUV Nord Ex ib IECEx Certificate of ConformityIECEx TUN 16.0023XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-2761AENGENGPDF192 KB