Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V |
|
Interface | ||
Programming interface | interface LPI | |
Input | ||
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode |
|
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.3, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode |
|
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Interface | omnidirectional dipole antenna, adjustable in vertical plane | |
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables |
|
Communication | WirelessHART specification IEC 62591 - Physical layer: IEEE 802.15.4.2006 - Frequency range: 2.4 GHz (ISM band, license-free) - Transfer rate: 250 kBit/s - Maximum transmission power: +10 dBm (EIRP) - Range: 250 m outdoors, 50 m indoors (under reference conditions) - Communications standard: WirelessHART |
|
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Display elements | green LED: battry status yellow LED: communication status red LED: device status |
|
Control elements | 1 push botton for: - device status - enter/leave configuration mode - join trigger - factory reset |
|
Configuration | wired interface: - HART 7.1, FSK compatible - transmission rate: 1200 Bit/s - used for device commissioning with an handheld terminal or a configuration tool (DTM) |
|
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 , FCC ID: SJC-M2140 | |
RoHS | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-64 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | max. 90 % , noncondensing | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Impact resistance | 15 g, 11 ms | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 |
|
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
Height | 192 mm | |
Width | 110.4 mm | |
Depth | 100.6 mm | |
Mounting | mounting on field device , panel or pole mounting |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
System | Classcode |
---|---|
ECLASS 13.0 | 27210192 |
ECLASS 12.0 | 27210192 |
ECLASS 11.0 | 27210192 |
ECLASS 10.0.1 | 27210190 |
ECLASS 9.0 | 27210190 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC001604 |
ETIM 8.0 | EC001604 |
ETIM 7.0 | EC001604 |
ETIM 6.0 | EC001604 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
The device upgrades a conventional HART or 4 mA ... 20 mA field device with a WirelessHART interface. It is mounted either directly to the cable gland entry or separated from the field device.
The device contains a battery pack which also powers the field device. Depending on the parameterization, battery lifetimes up to 5 years are possible. This allows autonomous measurements. The rotatable antenna can be brought in the optimal position, regardless of the mounting orientation of the field device.
The unit is easily programmed with a configuration tool (DTM or DD).
For additional information, refer to the manual and www.pepperl-fuchs.com.
System Descriptions | Språk | Filtype | Filstørrelse |
---|---|---|---|
Patent Information | ENG | 365 KB | |
Brief Instructions | |||
Brief Instructions - WirelessHART Adapter Firmware Update Instructions | ENG | 2449 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 124 KB | |
Manuals | |||
Manual WirelessHART Adapter WHA-ADP2-F8B2-*-**-Z1(-EX1) | ENG | 6584 KB |
Certificates | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
Canada, USA CSA Certificate of Compliance | CoC70130741(C) | ALL | 89 KB | |
Singapore IMDA Radio Approval | N2701-20 | ALL | 55 KB | |
Control Drawings | ||||
Control drawing CSA / Control drawing CSA | ALL | 140 KB |
Device Description Files/Drivers | Frigivelsesinfo | Filtype | Filstørrelse |
---|---|---|---|
DTM Collection WirelessHART V1.0.2.4 / DTM Collection WirelessHART V1.0.2.4 | ZIP | 22259 KB | |
DD Collection for WirelessHART / DD Collection für WirelessHART | ZIP | 3114 KB |