Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
Produktbeskrivelse |
---|
LCD batch controller with 6 optocoupler outputs and 90 ... 260 VAC supply voltage |
General specifications | ||
---|---|---|
Pre-selection | 6-fold | |
Data storage | > 10 years, EEPROM | |
Programming | keypad-driven menu | |
Indicators/operating means | ||
Type | 2-line, 2 x 6-digit LC display with leading sign Multicolor, backlit |
|
Display value | digit height 9 mm | |
Pre-selection | digit height 7 mm | |
Key interlock | via "high" potential at "LOCK" input | |
Decimal point | 0 to max 5 fractional digits | |
Scale factor | 0.0001 ... 99.9999 | |
Reset | manually or external | |
Electrical specifications | ||
Fusing | 90 … 260 V AC: T 0.1 A | |
Operating voltage | 90 ... 260 V AC | |
Power consumption | max. 8 VA | |
Input | ||
Connection | Counter inputs: A and B Control/reset inputs: LOCK, RESET, GATE, MPI |
|
Signal voltage | ||
High | 12 ... 30 V DC | |
Low | 0 ... 4 V DC | |
Counting frequency | max. 50 kHz | |
Minimum pulse duration | Control/reset inputs: 10 ms / 1 ms | |
Impedance | 5 kOhm | |
Count modes | ||
Pulse counter | Counting with counting direction (cnt.dir), difference counting (up.dn), up/down counting (quad), Cumulative counting (up.up), up/down counting x 2 (quad 2), up/down counting x 4 (quad 4), additional functions for counter input A and counter input B: |
|
Frequency counter | functions for input A and input B: |
|
Timer | Time measurement via GATE input (FrErun), counter input A: Start, counter input B: Stop (InpA.InpB.), counter input B: Start/Stop (InpB.InpB.), time measuring via RESET input (auto) |
|
Output | ||
Sensor supply | 20.4 ... 27.6 V DC, max. 80 mA |
|
Response time | Add/Sub/autorepeat < 6 ms A/B; (A-B)/A: < 23 ms |
|
Optocoupler | output 1 to 6, NPN-Opto coupler output 3 to 6 with common emitter Schaltleistung 30 V DC / 10 mA |
|
Signal voltage | UCESAT with IC = 10 mA: max. 2 V UCESAT with IC = 5 mA: max. 0.4 V |
|
Compliance with standards and directives | ||
Directive conformity | ||
Low Voltage Directive 2006/95/EC | EN 61010-1:2001; protection class: 2 | |
EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 50295:1999 | |
Standard conformity | ||
Emitted interference | DIN EN 55011:2009, Class B | |
Mech. capacity | EN 60068-2-6:2008 10 … 55 Hz / 1 mm / XYZ 30 min in each direction |
|
Shock and impact resistance | EN 60068-2-27:1995 100 G / 2 ms / XYZ 3 times in each direction |
|
Ambient conditions | ||
Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
Storage temperature | -25 ... 75 °C (-13 ... 167 °F) | |
Relative humidity | ≤ 93 % at 40 °C (noncondensing) |
|
Altitude | 0 ... 2000 m | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP65 (front) | |
Mass | approx. 151 g | |
Dimensions | 48 mm x 48 mm x 109.8 mm |
System | Classcode |
---|---|
ECLASS 13.0 | 27210301 |
ECLASS 12.0 | 27210301 |
ECLASS 11.0 | 27210301 |
ECLASS 10.0.1 | 27210301 |
ECLASS 9.0 | 27210301 |
ECLASS 8.0 | 27210301 |
ECLASS 5.1 | 27210301 |
ETIM 9.0 | EC002300 |
ETIM 8.0 | EC002300 |
ETIM 7.0 | EC002300 |
ETIM 6.0 | EC002300 |
ETIM 5.0 | EC000677 |
UNSPSC 12.1 | 41111902 |
Brief Instructions | Språk | Filtype | Filstørrelse |
---|---|---|---|
Programming diagram KC-LCDC-48-6T-* / Programmierdiagramm KC-LCDC-48-6T-* | ALL | 163 KB | |
Manuals | |||
Manual KC-LCDC-48-6T-* | ENG | 1718 KB |
Declaration of Conformity | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2895B | ALL | 110 KB |