Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | SL1: 1a(-), 1b(-); 2a(+), 2b(+) | |
Rated voltage | 19 ... 30 V DC bus powered via Termination Board | |
Ripple | ≤ 10 % | |
Rated current | ≤ 40 mA at 24 V | |
Power dissipation | ≤ 1 W at 20 mA and 500 Ω load | |
Power consumption | ≤ 1 W | |
Input | ||
Connection side | control side | |
Connection | SL1: 8a(+), 7a(-); 10a(+), 9a(-) | |
Input signal | 4 ... 20 mA , limited to approx. 30 mA | |
Input voltage | open loop voltage of the control system ≤ 30 V | |
Voltage drop | approx. 6 V at 20 mA | |
Input resistance | field wiring open circuit : > 100 kΩ field wiring < 50 Ω : > 100 kΩ when using terminals 5a, 5b; 1a, 1b |
|
Output | ||
Connection side | field side | |
Connection | SL2: 5a(+), 5b(-); 1a(+), 1b(-) SL2: 5b(-), 7a(+); 1b(-), 3b(+) (no short circuit detection) |
|
Voltage | ≥ 13 V at 20 mA | |
Current | 4 ... 20 mA | |
Load | 100 ... 650 Ω , for terminals 1a, 1b; 5a, 5b 0 ... 550 Ω , for terminals 1b, 3b; 5b, 7a |
|
Ripple | 20 mV rms | |
Line fault detection | breakage, load > 100 kΩ, short-circuit, load < 50 Ω | |
Fault indication output | ||
Connection | SL1: 6b | |
Output type | open collector transistor (internal fault bus) | |
Transfer characteristics | ||
Deviation | at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis |
|
Influence of ambient temperature | < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) | |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
|
Rise time | 10 to 90 % ≤ 10 ms | |
Galvanic isolation | ||
Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff | |
Output/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/input | functional insulation, rated insulation voltage 50 V AC | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 For further information see system description. |
|
Degree of protection | IEC 60529 | |
Protection against electrical shock | UL 61010-1:2012 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 140 g | |
Dimensions | 18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D) | |
Height | 114 mm | |
Width | 18 mm | |
Depth | 130 mm | |
Mounting | on termination board | |
Coding | pin 1 and 3 trimmed For further information see system description. |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | DEMKO 20 ATEX 2378 X | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Output | Ex ia, Ex iaD | |
Voltage | 25.2 V | |
Current | 93 mA | |
Power | 585.3 mW | |
Internal capacitance | 1.05 nF | |
Internal inductance | 0 | |
Supply | ||
Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) | |
Input | ||
Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) | |
Certificate | DEMKO 20 ATEX 2379 X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 | |
International approvals | ||
UL approval | E106378 | |
Control drawing | 116-0475 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx ULD 20.0012X | |
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex ec IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210120 |
ECLASS 12.0 | 27210120 |
ECLASS 11.0 | 27210120 |
ECLASS 10.0.1 | 27210120 |
ECLASS 9.0 | 27210120 |
ECLASS 8.0 | 27210120 |
ECLASS 5.1 | 27210120 |
ETIM 9.0 | EC002653 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
This isolated barrier is used for intrinsic safety applications.
The device repeats the input signal from a control system to drive HART I/P converters, electrical valves, and positioners located in a hazardous area.
Digital signals are superimposed on the analog values at the field side or control side and are transferred bi-directionally.
Current transferred across the DC/DC converter is repeated at the terminals 5a, 5b (1a, 1b). The terminals 5b, 7a (1b, 3b) are used when no short-circuit detection is required.
An open or short field circuit presents a high impedance to the control side to allow alarm conditions to be monitored by the control system.
Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault conditions are monitored via a Fault Indication Board.
This device mounts on a HiD Termination Board.
Safety and Security Documentation | Språk | Filtype | Filstørrelse |
---|---|---|---|
Instruction manual | ENG | 170 KB | |
Functional Safety Manual | ENG | 1969 KB | |
Manuals | |||
System Manual | ENG | 5438 KB |
CAD | Språk | Filtype | Filstørrelse |
---|---|---|---|
CAD 2-D / CAD 2-D | ALL | ZIP | 16364 KB |
Certificates | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
Canada, USA UL Hazardous Location Certificate of Compliance cULus UL E106378 | CoC E106378 RepRef E106378-20200610 | ALL | 236 KB | |
China SITIIAS CCC Ex Certificate | 2021322316003750 (Singapore) | ALL | 1058 KB | |
Europe DEMKO ATEX Category (1) D ATEX Category (M1) ATEX Category (1) G | DEMKO 20 ATEX 2378X | ALL | 57 KB | |
Europe DEMKO ATEX Category 3 G | DEMKO 20 ATEX 2379X | ALL | 50 KB | |
UL IECEx Certificate of Conformity | IECEx ULD 20.0012X | ALL | LINK | --- |
Worldwide TUV Rheinland Functional Safety Certificate | TÜV-Rheinland 968/FSP 2066.00/20 | ALL | 650 KB | |
Control Drawings | ||||
Control drawing UL / Control drawing UL | ALL | 27 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-4802A | ALL | 81 KB |