Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
Supply | ||
---|---|---|
Connection | terminals 1, 2 | |
Rated voltage | 8 ... 35 V DC 8 ... 30 V DC for hazardous area |
|
Input | ||
Sensor types | resistance thermometer (RTD): - Pt100, Pt500, Pt1000 acc. to IEC 751 and Ni100, Ni500, Ni1000 acc. to DIN 43760 resistance transmitter (Ω) thermocouple (TC): - B (PtRh30-PtRh6), C (W5Re-W26Re), D (W3Re-W25Re), E (NiCr-CuNi), J (Fe-CuNi), K (NiCr-Ni), L (Fe-CuNi), N (NiCrSi-NiSi), R (PtRh13-Pt), S (PtRh10-Pt), T (Cu-CuNi), U (Cu-CuNi), MoRe5-MoRe41 acc. to IEC 584, part 1 voltage transmitter (mV) |
|
Connection | resistance thermometer (RTD): - 2-wire connection: terminals 3, 6 - 3-wire connection: terminals 3, 5, 6 - 4-wire connection: terminals 3, 4, 5, 6 resistance transmitter (Ω): - 2-wire connection: terminals 3, 6 - 3-wire connection: terminals 3, 5, 6 - 4-wire connection: terminals 3, 4, 5, 6 thermocouple (TC): terminals 4, 6 |
|
Cold junction compensation | internal (Pt100) or external (0 ... 80 °C (273 ... 353 K)), accuracy ± 1 K | |
Lead resistance | resistance thermometer (RTD): max. 11 Ω per line | |
Current | resistance thermometer (RTD): sensor current ≤ 0.6 mA thermocouple (TC): sensor current 30 mA |
|
Output | ||
Connection | terminals 1, 2 | |
Current limit | ≤ 25 mA | |
Load | (Vs - 8)/0.025 A | |
Switch-on delay | 4 s , during power up Ia = 3.8 mA | |
Output signal | 4 ... 20 mA, 20 ... 4 mA temperature linear, resistance linear, voltage linear | |
Residual ripple | Upp ≤ 5 V at Ub ≥ 13 V, fmax = 1 kHz | |
Response time | 1 s | |
Self current consumption | max. 3.5 mA | |
Signal on alarm | measuring range undercut: linear drop to 3.8 mA exceeding measuring range: linear rise to 20.5 mA sensor breakage, sensor short circuit: ≤ 3.6 mA oder ≥ 21.0 mA can be set up |
|
Galvanic isolation | ||
Input/Output | safe galvanic isolation acc. to EN 50020, 3.75 kV AC | |
Measurement accuracy | ||
Reference operating conditions | calibration temperature 23 °C (296 K) ± 5 K | |
Maximum measured error | resistance thermometer (RTD): 0.2 ... 0.5 K or 0.08 ... 0.2 % resistance transmitter (Ω): ± 0.1 ... 1.5 Ω or 0.08 ... 0.12 % thermocouple (TC): typ. 0.5 ... 2.0 K or 0.08 % voltage transmitter: ± 20 µV or 0.08 % |
|
Operating conditions | ||
Ambient conditions | ||
Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) , for hazardous area see certificate | |
Storage temperature | -40 ... 100 °C (-40 ... 212 °F) | |
Vibration resistance | 4 g/2 ... 150 Hz | |
Relative humidity | moisture condensation allowable | |
Mechanical specifications | ||
Degree of protection | IP00/IP66 installed | |
Connection | Terminals for wires max. 1.75 mm 2, undetachable screws | |
Material | housing: PC potting: PUR |
|
Mass | approx. 40 g | |
Dimensions | ∅44 x 22,5 mm (1.7 x 0.9 inch) | |
Mechanical construction | ||
Construction type | connection head acc. to DIN 43729 form B, field housing | |
Indication and operation | ||
Configuration | via PC operating software, configuration set TXU 10L interface: PC interface connection cable TTL-/-RS 232 with plug |
|
Certificates and approvals | ||
Explosion-hazardous area | ZELM 07 ATEX 0352 X , for additional certificates see www.pepperl-fuchs.com | |
Type of protection | II 1G Ex ia IIC T6/T5/T4 | |
General information | ||
Directive conformity | ||
Directive 2004/108/EC (EMC) | emitted interference and noise immunity to EN 61326-1:2006 and EN 61326-2-3:2006 | |
Directive 94/9/EC (ATEX) | EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | EN 60529 | |
Climate class | EN 60654, class C | |
Vibration resistance | EN 60068-2-6 | |
Supplementary documentation | technical information TI070O operating instructions KA141O safety information SI085O (ZELM 07 ATEX 0352 X) |
|
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27200591 |
ECLASS 12.0 | 27200591 |
ECLASS 11.0 | 27200591 |
ECLASS 10.0.1 | 27200591 |
ECLASS 9.0 | 27200591 |
ECLASS 8.0 | 27200591 |
ECLASS 5.1 | 27200591 |
ETIM 9.0 | EC001447 |
ETIM 8.0 | EC001447 |
ETIM 7.0 | EC001447 |
ETIM 6.0 | EC001447 |
ETIM 5.0 | EC001447 |
UNSPSC 12.1 | 41111950 |
The temperature head transmitter linearises the signal from resistance sensors (RTD) and provides a 4 mA ... 20 mA current output. The input circuit is galvanically isolated from the output circuit.
The device is intrinsically safe in accordance with EEx ia IIC. The temperature head transmitter may be configured in situ with a programming socket to operate over the desired temperature range with a Pt100.
Setting up of the transmitter is done using the TXU10L configuration kit.
The transmitter is polarity protected and will not be damaged by connecting the power supply with the wrong polarity. The maximum load in the output loop depends on the supply voltage.
Brief Instructions | Språk | Filtype | Filstørrelse |
---|---|---|---|
KA141O, brief instructions HUT-Ex / KA141O, Kurzanleitung HUT-Ex | ALL | 334 KB | |
Safety and Security Documentation | |||
Instruction manual SI085O, HUT-Ex / Betriebsanleitung SI085O, HUT-Ex | ALL | 732 KB |
Certificates | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
Europe ZELM ATEX Category 1 G | ZELM 07 ATEX 0352 X | ALL | 1163 KB |