Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
Produktbeskrivelse |
---|
Multi-input/output for digital signals, stand-alone device with aluminum housing for field installation |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installation in hazardous area | Zone 1 / Div. 1 | |
Electronic component | Binary multi-input/output R8D0-MIO-Ex12.PA* For technical data on installed electronic component see datasheet. | |
Fieldbus connection | ||
Fieldbus type | PROFIBUS PA | |
Digital input | ||
Number of inputs | 12 | |
Galvanic isolation | ||
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | ≤ 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 10 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Cable diameter | see table 2 | |
Cable gland | sensor inputs M16, fieldbus M20 | |
Housing material | Aluminum | |
Degree of protection | IP66 | |
Mass | 1800 g | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BVS 16 ATEX E 075 X | |
Marking | II 2 (1) G Ex ib [ia Ga] IIC T4 Gb , II 3 (1) G Ex ic [ia Ga] IIC T4 Gc , II 3 (1) G Ex ec [ia Ga] IIC T4 Gc , I (M1) [Ex ia Ma] I , II (1) D [Ex ia Da] IIIC , II 2 (1) D Ex tb [ia Da] IIIC T130 °C Db | |
Bus | FISCO see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
FM approval | pending | |
IECEx approval | IECEx BVS 16.0051X | |
Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Ma] I , [Ex ia Da] IIIC , Ex tb [ia Da] IIIC T130 °C Db | |
Certificates and approvals | ||
Marine approval | pending | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242610 |
ETIM 9.0 | EC001601 |
ETIM 8.0 | EC001601 |
ETIM 7.0 | EC001601 |
ETIM 6.0 | EC001601 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
This fieldbus junction box holds a multi-input/output (MIO) for transferring signals from discrete inputs and valves to the control system. The MIO offers the same functionality as the components FD0‑VC‑Ex* and FD0‑BI‑*. The fieldbus junction box can be installed in Zone 1/Div. 1 with sensors and actuators located in Zone 0/Div. 1.
The housing, type F2, is made of sturdy cast aluminum for installation in rough environments. Fieldbus and field device entrances can be selected individually from a range of cable glands. Optionally, either screw terminals or spring terminals can be chosen.
Literature | Språk | Filtype | Filstørrelse |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Språk | Filtype | Filstørrelse |
---|---|---|---|
Instruction manual | ENG | 174 KB | |
Manuals | |||
Manual | ENG | 5008 KB | |
Software Information | |||
Release information Device Description (EDDL) for Siemens SIMATIC PDM | ENG | 1127 KB |
CAD | Språk | Filtype | Filstørrelse |
---|---|---|---|
CAD-files 2-D / CAD-Dateien 2-D | ALL | ZIP | 538 KB |
Certificates | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
Brasil TUV Rheinland Brazil | TÜV 17.2298 X | ALL | 1257 KB | |
Canada FM | FM19CA0042X | ALL | 1698 KB | |
China SITIIAS CCC Ex Certificate | 2021322314004067 (Singapore) | ALL | 1616 KB | |
Europe ATEX | BVS 16 ATEX E 075 X | ALL | 1629 KB | |
IECEx Certificate of Conformity | IECEx BVS 16.0051X | ALL | LINK | --- |
Thorsis Techn SIMATIC PDM | SIMATIC PDM - Do-MIO-EX12.PA | ALL | 106 KB | |
USA FM | FM19US0077X | ALL | 1700 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-3160D | ALL | 1064 KB |
Device Description Files/Drivers | Frigivelsesinfo | Filtype | Filstørrelse |
---|---|---|---|
GSD / GSD | Rev 1.0 | ZIP | 7 KB |
DTM Collection FieldConnex / DTM Collection FieldConnex | 1.9.0.2268 | ZIP | 35363 KB |
Device Description (EDDL) for Siemens SIMATIC PDM / Gerätebeschreibung (EDDL) für Siemens SIMATIC PDM | 1.0.0.1532 | ZIP | 359 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
FieldConnex® Multi-Input/Output