Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
Produktbeskrivelse |
---|
Module for use with Segment Protectors |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Fieldbus connection | ||
Field-side | ||
Connection | terminals 10+, 11-, 12S | |
Rated voltage | Uin - Uout 0.9 ... 1.8 V | |
Rated current | max. 1 A | |
Host-side | ||
Connection | terminals 7+, 8-, 9S | |
Rated voltage | 9 ... 32 V DC | |
Rated current | max. 1 A | |
Power dissipation | max. 1.8 W | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 75 % | |
Pollution degree | max. 2, according to IEC 60664 | |
Mechanical specifications | ||
Connection type | Terminals | |
Core cross section | up to 2.5 mm2 | |
Housing | 20 mm x 115 mm x 107 mm | |
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
Certificate | PF 16 CERT 1030 X | |
Marking | II 3 G Ex ec IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 | |
General information | ||
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 19170104 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC002584 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Pepperl+Fuchs Segment Protectors feature a safety switch off for explosion protection at typically 31.5 V.
In rare cases the tolerances in other manufacturers’ power modules in combination with very short cable lengths with little or no voltage drop lead to a switch off of the Segment Protector.
The KLD0-SAA is used to limit the voltage to uncritical values.
The KLD0-SAA is installed in close proximity to the power supply within the control cabinet.
Literature | Språk | Filtype | Filstørrelse |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Språk | Filtype | Filstørrelse |
---|---|---|---|
Instruction manual | ENG | 51 KB |
Certificates | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
Europe Pepperl+Fuchs ATEX Category 3 G Declaration of Conformity | PF16CERT1030X | ALL | 192 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2528C | ALL | 1039 KB |