Teknisk support Industrielle sensorer
Kundeservice, eksplosjonsbeskyttelse

SMART Transmitter Power Supply HiC2025

HiC2025
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Input for 2-wire SMART transmitters and current sources
  • Output for 4 mA ... 20 mA or 1 V ... 5 V
  • Low power dissipation
  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Last ned komplett datablad som PDF:


Datablad utdrag: Tekniske data for  HiC2025

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 45 mA at 24 V and 20 mA source mode output
Power dissipation≤ 800 mW
Power consumption≤ 1.1 W
Input
Connection sidefield side
ConnectionSL2: 5a(+), 1b(-); 5a(+), 5b(-)
Input signal4 ... 20 mA limited to approx. 26 mA
Voltage dropapprox. 5 V on SL2: 5a(+), 1b(-)
Available voltage≥ 15 V at 20 mA , ≥ 18 V at 4 mA on SL2: 5a(+), 5b(-)
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-)
Load0 ... 350 Ω (source mode)
Output signalsource mode: 4 ... 20 mA or 1 ... 5 V (internal resistor: 250 Ω, 0.1 %)
sink mode: 4 ... 20 mA, operating voltage 10 ... 30 V
For additional internal or external loads the voltage drop has to be considered, e. g. 250 Ω x 20 mA = 5 V.
Ripple20 mV rms
Transfer characteristics
Deviationat 20 °C (68 °F)
< 0.1 % of full scale, incl. non-linearity and hysteresis (source mode and sink mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode and sink mode 4 ... 20mA)
< 0.5 mV/K (-20 ... 70 °C (-4 ... 158 °F)); < 1 mV/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode 1...5 V)
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling time≤ 50 ms
Rise time/fall time≤ 10 ms
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff
Indicators/settings
Display elementsLED
Control elementsDIP switch
Factory settingoutput: current source
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
EN 61326-3-2:2018
For further information see system description.
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 017
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Supply
Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
EquipmentSL2: 5a(+), 5b(-)
Voltage25.2 V
Current100 mA
Power630 mW
Internal capacitance5.7 nF
Internal inductancenegligible
EquipmentSL2: 5a(+), 1b(-)
Voltage30 V
Current128 mA
Voltage7.2 V
Current100 mA
Power25 mW
Internal capacitance5.7 nF
Internal inductancenegligible
CertificateCESI 19 ATEX 027 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
International approvals
FM approval
FM certificateFM 19 US 0122 X , FM 19 CA 0065 X
Control drawing116-0470 (cFMus)
UL approvalE106378
Control drawing116-0458 (cULus)
IECEx approval
IECEx certificateIECEx CES 06.0002X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2025

Function

This isolated barrier is used for intrinsic safety applications.

The device supplies 2-wire transmitters in the hazardous area, and can also be used with current sources.

It transfers the analog input signal to the safe area as an isolated current value.

Bi-directional communication is supported for SMART transmitters that use current modulation to transmit data and voltage modulation to receive data.

The output is selected as a current source, current sink, or voltage source via DIP switches.

This device mounts on a HiC Termination Board.

Product Documentation: HiC2025

Velg språk:
Safety and Security DocumentationSpråkFiltypeFilstørrelse
Instruction manualENGPDF170 KB
Functional Safety ManualENGPDF2002 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2025

Velg språk:
CADSpråkFiltypeFilstørrelse
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---

Approvals: HiC2025

Velg språk:
CertificatesSertifikatnummerSpråkFiltypeFilstørrelse
Brasil TUV Rheinland BrazilTÜV 16.0820ALLPDF1160 KB
CESI IECEx Certificate of ConformityIECEx CES 06.0002XALLLINK---
Canada FMFM19CA0065XALLPDF374 KB
China SITIIAS CCC Ex Certificate2020322316001223 (Singapore)ALLPDF1616 KB
Europe CESI ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GCESI 06 ATEX 017ALLPDF788 KB
Europe CESI ATEX Category 3CESI 19 ATEX 027XALLPDF492 KB
KIWA IECEx Certificate of Conformity Zone 2IECEx KIWA 15.0017XALLLINK---
Korea KOSHA15-AV4BO-0594ALLPDF661 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20190911 - E106378 RepRef 20190903ALLPDF613 KB
USA FMFM19US0122XALLPDF346 KB
United Arab Emirates SGS Gulf Limited ECASEx23-12-96805/E23-12-100057/NB0002ALLPDF603 KB
United Kingdom CML UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 21UKEX2939ALLPDF195 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF54 KB
Control drawing FM / Control drawing FM   ALLPDF35 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4563BALLPDF82 KB
UKCA-Declaration of conformity / UKCA-KonformitätserklärungDOC-5712ALLPDF73 KB

Relaterte produkter: HiC2025

Accessory of

System board for Schneider, Foxboro FBM series, For 8 modules, For 8-channel cards FBM201/214(b)/216(b) (AI), FBM215/218/237 (AO), FBM204/205 (AO/AI), FBM244 (AI/AO), FBM247/248 (UIO), 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2031 (AO), HiC2081 (TI), HiC2831R5 (DI), HiC2883 (DO), HiC2441 (UIO), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 25-pin, Number of modules: 8, Signal type: Universal, Manufacturer: Foxboropa
System board for Yokogawa ProSafe-RS, For 16-channel AI card SAI143, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: ProSafe-RSpa
System board for Yokogawa CENTUM VP, For 8-channel AI card AAI135, For 8-channel AI/AO card AAI835, For 8 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 8, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Yokogawa CENTUM VP, For 16-channel AI cards AAI143, AAB141-H, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Yokogawa CENTUM VP, For 16-channel AI card AAI141, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Yokogawa CENTUM VP, For 16-channel AI/AO card AAB841, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Yokogawa CENTUM VP, For 16-channel AI/AO card AAI841, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2031 (AO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input/analog output, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Yokogawa CENTUM VP, For 16-channel AI card AAV141, For 16 modules, Recommended module: HiC2025(A) (AI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 40-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Schneider, Foxboro FBM series, For 16 modules, For 16-channel AI card FBM211, 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Foxboro, Control system type: FBMpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3700A, and 3721, For 16 modules, Recommended modules: HiC2025(A) (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Triconpa
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 16-channel universal I/O card 3902(A)X and AO card 3809(A)X, For 16 modules, Supported signal types: DI/DO/AI/TI/AO/UIO, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 50-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Analog output
Universal, Manufacturer: Triconex, Control system type: Tricon CXpa
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CXpa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.