Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Last ned komplett datablad som PDF:
Supply | ||
---|---|---|
Nominal voltage | 24 V DC | |
Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
Power dissipation | 0.7 W , with Multiplexer | |
Reverse polarity protection | yes | |
HART signal channels (intrinsically safe) | ||
HART signal channels | ||
Number of channels | 32 unbalanced signal loops | |
Interface | ||
Type/number | 2 x RS-485 | |
Redundancy | ||
Supply | yes | |
Galvanic isolation | ||
HART signal channels | 30 V DC | |
Ambient conditions | ||
Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
Relative humidity | 5 ... 90 %, non-condensing | |
Mechanical specifications | ||
Core cross section | 2.5 mm2 (16 AWG) | |
Connection | field side: fixed screw terminals control side: fixed screw terminals RS 485 interface: removable screw terminals power: removable screw terminals |
|
Mass | approx. 500 g | |
Dimensions | 222 x 122 x 208 mm (8.7 x 4.8 x 8.2 inch) (W x H x D) , depth including module assembly with HiDMux2700 | |
Height | 122 mm | |
Width | 222 mm | |
Depth | 208 mm | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
Certificate | CML 17ATEX3337X II 3 G Ex ec IIC T4 Gc |
|
Certificate | IECEx CML 17.0178X Ex ec IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210190 |
ECLASS 12.0 | 27210190 |
ECLASS 11.0 | 27210190 |
ECLASS 10.0.1 | 27210190 |
ECLASS 9.0 | 27210190 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27242690 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121008 |
This HART Termination Board has 32 terminal blocks to connect up to 32 HART field devices.
It contains one slot to mount the 32-channel HART Multiplexer Master type HiDMux2700.
The Termination Board can be used for general-purpose applications or in conjunction with intrinsic safety barriers for hazardous applications.
It offers fused redundant power supply connections. RS 485 terminals are redundant and can be daisy chained.
Safety and Security Documentation | Språk | Filtype | Filstørrelse |
---|---|---|---|
Instruction manual | ENG | 162 KB | |
Manuals | |||
Installation Manual HISHPSM/32/MM-01 | ENG | 1570 KB | |
Manual DTM description HiDMux2700 | ENG | 2278 KB | |
Manual HiDMux2700 | ENG | 8581 KB |
Certificates | Sertifikatnummer | Språk | Filtype | Filstørrelse |
---|---|---|---|---|
ATEX Certificate | CML 17 ATEX 3337X | ALL | 126 KB | |
China SITIIAS CCC Ex Certificate | 2023322308005457 (Singapore) | ALL | 763 KB | |
IECEx Certificate of Conformity | IECEx CML 17.0178X | ALL | LINK | --- |
Korea Radio Approval | KCC-REI-PF1-HISHPSM-32-MM | ALL | 454 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-B0C1B | ALL | 43 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-B0G3 | ALL | 40 KB |