Teknisk support Industrielle sensorer
Kundeservice, eksplosjonsbeskyttelse

Surge Protector M-LBAS-IA1.IE

FieldConnex®
M-LBAS-IA1.IE
  • For Ethernet-APL spur ports
  • Intrinsically safe according to 2-WISE and FISCO
  • Installation on DIN mounting rail in cabinet or field junction box
  • Grounding of the cable shield via a gas discharge tube

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Last ned komplett datablad som PDF:


Datablad utdrag: Tekniske data for  M-LBAS-IA1.IE

Produktbeskrivelse
Surge protector, Ethernet-APL, control cabinet installation, Ex ia, Ex ec, indirect shield grounding
General specifications
Design / MountingCabinet installation
Installation in hazardous areaZone 1
Ethernet Interface
Interface typeEthernet-APL auxiliary device
Electrical specifications
Rated voltage30 V
Rated current500 mA
Impulse rating2 kV/1 kA (category C1) per line
10 kV/5 kA (category C2) per line
1 kA (category D1) per line
Impulse discharge current (10/350 µs)0.5 kA per line
Nominal discharge current (8/20 µs)
per line5 kA
total10 kA
Shield10 kA
Max. surge current (8/20 µs)10 kA overstressed fault mode 3 acc. to IEC 61643-21
Voltage protection level
Line/Earthmax. 1500 V C1 , 1 kA per line
max. 2100 V C2 , 5 kA per line
max. 50 V C3 , 50 A per line
max. 1300 V B2 , 50 A per line
Shield/Earthmax. 1500 V C1 , max. 1800 V C2 , max. 50 V C3 , max. 1300 V B2
Standard conformity
Degree of protectionIEC/EN 60529
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Surge protectionIEC 61643-21
EthernetEthernet-APL ,
IEEE 802.3 for 10BASE-T1L
Ambient conditions
Ambient temperature-40 ... 80 °C (-40 ... 176 °F)
Storage temperature-50 ... 90 °C (-58 ... 194 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Mechanical specifications
Connection typescrew terminals
Core cross sectionsolid wire 0.5 ... 2.5 mm2 ,
stranded wire 0.5 ... 1.5 mm2
Housing materialPolyamide PA 6.6
Degree of protectionIP20
Mass32 g
MountingDIN mounting rail
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 22 ATEX 8786 X , TÜV 22 ATEX 8816 X
Marking2-WISE auxiliary device , FISCO
MarkingEx-Hexagon ll 3 G Ex ec llC T6 Gc ,
Ex-Hexagon ll 2 (1) G Ex ia [ia Ga] IIC T6 Gb ,
Ex-Hexagon ll 2 (1) D Ex ia [ia Da] lIIC T80°C Db ,
Ex-Hexagon l M2 (M1) Ex ia [ia Ma] l Mb
Voltage30 V
Current500 mA
Internal capacitancenegligible 0 nF
Internal inductancenegligible 0 µH
Directive conformity
Directive 2014/34/EUEN 60079-0:2018 ,
EN 60079-11:2012 ,
IEC TS 60079-47:2021
Supplementary information
International approvals
IECEx approvalIECEx TUR 22.0017X
Approved forEx ec llC T6 Gc ,
Ex ia [ia Ga] IIC T6 Gb ,
Ex ia [ia Da] lIIC T80°C Db ,
Ex ia [ia Ma] l Mb
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027171202
ECLASS 12.027171202
ECLASS 11.027130805
ECLASS 10.0.127130805
ECLASS 9.027130805
ECLASS 8.027130805
ECLASS 5.127130801
ETIM 9.0EC000941
ETIM 8.0EC000941
ETIM 7.0EC000941
ETIM 6.0EC000941
ETIM 5.0EC000941
UNSPSC 12.139121610

Details: M-LBAS-IA1.IE

Function

The surge protector protects spur ports of Ethernet-APL field switches used with Ethernet-APL field devices and PROFIBUS PA field devices.

The surge protector directs power from voltage surges and lightning to earth via gas discharge tubes.

The cable shield is grounded through a gas discharge tube, thus allowing capacitive coupling of the cable shield at the protected Ethernet-APL field switch port.

The device is certified intrinsically safe for circuits in explosion-hazardous areas Zone 0 ... 2 according to 2‑WISE and FISCO. The surge protector can be installed in Zone 1 ... 2.

Mounting on a 35 mm DIN mounting rail permits installation in cabinets or fieldbus junction boxes.

Informative Literature: M-LBAS-IA1.IE

Velg språk:
LiteratureSpråkFiltypeFilstørrelse
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: M-LBAS-IA1.IE

Velg språk:
Safety and Security DocumentationSpråkFiltypeFilstørrelse
Instruction manualENGPDF164 KB
Manuals
ManualENGPDF1648 KB

Design / Simulation: M-LBAS-IA1.IE

Velg språk:
CADSpråkFiltypeFilstørrelse
CAD 3-D / CAD 3-DALLSTP3749 KB

Approvals: M-LBAS-IA1.IE

Velg språk:
CertificatesSertifikatnummerSpråkFiltypeFilstørrelse
China SITIIAS CCC Ex Certificate2022322304004748 (Singapore)ALLPDF1107 KB
Europe TUV Rheinland ATEX Certificate Surge Protective Device ATEX Category 2 (1)TÜV 22 ATEX 8786 XALLPDF1538 KB
Europe TUV Rheinland Surge Protective Device ATEX Category 3 G TÜV AtexTÜV 22 ATEX 8816 XALLPDF171 KB
Worldwide TUV Rheinland Surge Protective Device IECEx Certificate of ConformityIECEx TUR 22.0017XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-5856_ENGENGPDF176 KB

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …