Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Tam veri sayfasını PDF olarak indirin:
Veri sayfası alıntısı: Teknik veriler
NJ8-18GK-SN-10M
General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR with safety function |
Rated operating distance | 8 mm |
Installation | non-flush |
Assured operating distance | 0 ... 6.48 mm |
Reduction factor rAl | 0.4 |
Reduction factor rCu | 0.3 |
Reduction factor r304 | 0.85 |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Switching frequency | 0 ... 200 Hz |
Current consumption | |
| Measuring plate not detected | ≥ 3 mA |
| Measuring plate detected | ≤ 1 mA |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
MTTFd | 11850 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Standards | EN IEC 60947-5-2 |
Approvals and certificates |
IECEx approval | |
| Equipment protection level Ga | IECEx PTB 11.0092X |
| Equipment protection level Gb | IECEx PTB 11.0092X |
| Equipment protection level Gc (ec) | IECEx TUR 21.0017X |
| Equipment protection level Da | IECEx PTB 11.0092X |
| Equipment protection level Dc (tc) | IECEx TUR 21.0018X |
| Equipment protection level Mb | IECEx PTB 11.0092X |
ATEX approval | |
| Equipment protection level Ga | PTB 00 ATEX 2049 X |
| Equipment protection level Gb | PTB 00 ATEX 2049 X |
| Equipment protection level Gc (ec) | TÜV 20 ATEX 8523 X |
| Equipment protection level Da | PTB 00 ATEX 2049 X |
| Equipment protection level Dc (tc) | TÜV 20 ATEX 8524 X |
UL approval | cULus Listed, General Purpose |
| Ordinary Location | E87056 |
| Hazardous Location | E501628 |
| Control drawing | 116-0454 |
CCC approval | |
| Hazardous Location | 2020322315002308 |
NEPSI approval | |
| NEPSI certificate | GYJ16.1392X |
Ambient conditions |
Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) |
Mechanical specifications |
Connection type | cable |
Housing material | Crastin (PBT), black |
Sensing face | Crastin (PBT), black |
Degree of protection | IP68 |
Cable | |
| Cable diameter | 6 mm ± 0.2 mm |
| Bending radius | > 10 x cable diameter |
| Material | silicone |
| Core cross section | 0.75 mm2 |
| Length | 10 m |
Dimensions | |
| Length | 39 mm |
| Diameter | 18 mm |
General information |
Use in the hazardous area | see instruction manuals |
Classifications
System | Classcode |
ECLASS 13.0 | 27274101 |
ECLASS 12.0 | 27274101 |
ECLASS 11.0 | 27272401 |
ECLASS 10.0.1 | 27272401 |
ECLASS 9.0 | 27272401 |
ECLASS 8.0 | 27272401 |
ECLASS 5.1 | 27272401 |
ETIM 9.0 | EC002714 |
ETIM 8.0 | EC002714 |
ETIM 7.0 | EC002714 |
ETIM 6.0 | EC002714 |
ETIM 5.0 | EC002714 |
UNSPSC 12.1 | 39121550 |
Details:
NJ8-18GK-SN-10M
Product Documentation:
NJ8-18GK-SN-10M
Safety and Security Documentation | Dil | Dosya Tipi | Dosya Boyutu |
Talimatlar | TUR | PDF | 261 KB
|
Design / Simulation:
NJ8-18GK-SN-10M
Approvals:
NJ8-18GK-SN-10M
İlişkili Ürünler:
NJ8-18GK-SN-10M
Accessories |
|
|
|
Mounting flange, 18 mm, Retainer for all cylindrical sensors with M18 thread, Simple installation and exact setting, Large sensing range (max. 20 mm)fa |
|