Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Tam veri sayfasını PDF olarak indirin:
Ürün Açıklaması |
---|
Switch cabinet module 2 analog Inputs |
General specifications | ||
---|---|---|
Node type | Standard node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 | |
MTBF | 154 a | |
Indicators/operating means | ||
LED FAULT | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault |
|
LED INT | Internal input supply active; LED green | |
LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error |
|
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED IN | status of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range |
|
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 70 mA (without sensors) / max. 200 mA | |
Protection class | III | |
Current consumption | IAUX ≤ 650 mA | |
Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) | |
Input | ||
Number/Type | 2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V |
|
Supply | From AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX) | |
Current loading capacity | ≤ 100 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA From auxiliary voltage UAUX (AUX switch position) , overload and short-circuit protected |
|
Input resistance | current input: max. 70 Ω voltage input: 100 kΩ |
|
Accuracy | 0.1 % of input signal range at 25 °C (298 K) | |
Resolution | 15 Bit | |
Temperature influence | 0.0025 %/K of input signal range | |
Output | ||
Temperature influence | 1 µA/K or 0,3 mV/K | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.3.D | |
IO code | 7 | |
ID code | 3 | |
ID1 code | F | |
ID2 code | D | |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. | |
Parameter bits (programmable via AS-i) | function | |
P0 | 50/60 Hz filter P0=1, enabled P0=0, disabled |
|
P1 | projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected |
|
P2 | Indication of the peripheral fault by exceeding measuring range P2=1, peripheral fault is reported P2=0, peripheral fault is not reported |
|
P3 | P3=1, normal operating mode P3=0, both channels in current mode and without recognition of wire breakage |
|
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 |
|
Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
|
Material | ||
Housing | PA 66-FR | |
Mass | 110 g | |
Dimensions | ||
Height | 100 mm | |
Width | 18.9 mm | |
Length | 124 mm | |
Mounting | DIN mounting rail | |
Note | Max. length of jumpers = 5 cm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242601 |
ECLASS 12.0 | 27242601 |
ECLASS 11.0 | 27242601 |
ECLASS 10.0.1 | 27242601 |
ECLASS 9.0 | 27242601 |
ECLASS 8.0 | 27242601 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001596 |
ETIM 8.0 | EC001596 |
ETIM 7.0 | EC001596 |
ETIM 6.0 | EC001596 |
ETIM 5.0 | EC001596 |
UNSPSC 12.1 | 39121535 |
The AS-Interface connecting module VBA-2E-KE5-IJL/UJL is a switch cabinet module with 2 analog outputs for voltage or current. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping it onto the 35 mm DIN rail in compliance with EN 50022.
The connection is made via removable 4-pin push-in terminal blocks. For AS-i+, AS-i-, AUX+, and AUX-, two connections are available in each case; these connections are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded.
The supply to the inputs and the connected sensors can be fed either from the internal supply of the module from the AS-Interface or via an external UAUX auxiliary voltage. A switch located on the side of the module changes the source.
The relevant IN LED displays the current status of the inputs. If input signals are valid, the corresponding IN LED lights up permanently. If signals are outside the measuring range, the corresponding IN LED flashes.
The analog values are transmitted asynchronously with a data width of 16 bits as defined by AS-Interface profile 7.3. The value range of the current input is 0… 20,000 without wire break detection and 4000… 20,000 with wire break detection. The value range of the voltage input is 0 … 10,000.
Grid failures can be filtered using a parameterizable filter at 50 Hz or 60 Hz.
Notes:
Overloading of the internal input supply, absence of the external UAUX voltage source, measuring overrange, and a wire break at the current input are reported as peripheral faults to the AS-Interface master.
If the wire break detection is disabled, the extended current measuring range can be used.
A jumper between GND and 1CH or the parameter P1 can deactivate input channel 2. The jumper has priority here. If no jumper is set and P1 = 1, then both channels are active. Do not connect the 1CH and GND connections to external potentials. The length of the jumpers must not exceed 5 cm.
Brief Instructions | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 133 KB | |
Manuals | |||
Manual VBA-2E-KE5-IJL/UJL | ENG | 1586 KB |
CAD | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 19087 KB |
Certificates | Sertifika No. | Dil | Dosya Tipi | Dosya Boyutu |
---|---|---|---|---|
US CA UL | E223772 | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 128901 | ALL | 134 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-3534A | ALL | 108 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
AS-Interface Pano Modülü KE5 – Basit Kullanım ve Daha Fazla Yönetilebilirlik
Yeni KE5 pano modülünün özgün gövde tasarımı, belirgin bir görünürlük sağlamanın yanı sıra panoların ve bağlantı kutularının içinde montajı, kablolamayı ve bakımı kolaylaştırır.