选择您所在的国家/地区
K-LB-2.30G Surge Protection Barrier
主要优势一览
- 2-channel
- Mounting on DIN mounting rail
- For intrinsically safe or non-intrinsically safe 30 V applications
- Protects field or control circuit inputs
- Max. surge current (8/20 µs) 20 kA
- Uninterruptable operation (auto reset)
- Up to SIL 3 acc. to IEC/EN 61508
显示详情


注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
DE
- DE
- EN
- ES
- FR
- PL
K-LB-2.30G 技术数据
Number of protected signal lines | 4 | |
Topology | grounded |
Safety Integrity Level (SIL) | SIL 3 |
Connection | protected area: terminals 5, 6; 7, 8 unprotected area: terminals 1, 2; 3, 4 | |
Rated current | Ir | 250 mA |
Leakage current | < 10 µA at 24 V and 25 °C (77 °F) , line-line | |
Nominal voltage | 24 V DC | |
Maximum continuous operating voltage | Uc | 30 V DC |
Series resistance | < 0.5 Ω per line | |
Impulse rating | 10 kV/5 kA (category C2) 2 kV/2 kA (category D1) | |
Impulse discharge current (10/350 µs) | Iimp | 2 kA per line (2x) |
Nominal discharge current (8/20 µs) | In | 5 kA per line (10x) |
Rated surge current (8/20 µs) | ISM | 10 kA per line (1x) |
Total discharge current (8/20 µs) | Itotal | 20 kA (1x) |
Voltage protection level | Up | max. 100 V line-line for nominal discharge current In max. 50 V line-earth for nominal discharge current In |
Impulse reset time | < 30 ms | |
Insertion loss | ≤ 0.05 dB, at 0 ... 4 kHz, in 600 Ω-System ≤ 3 dB, at 0 ... 174 kHz, in 100 Ω-System |
Labeling | space for labeling at the front |
Degree of protection | IEC 60529:2013 | |
Surge protective devices for low voltage | EN 61643-21:2001+A1:2009+A2:2013 IEC 61643-21:2001+A1:2008+A2:2012 |
Installation conditions | |||||
|
Ambient temperature | -30 ... 80 °C (-22 ... 176 °F) For usage in hazardous area observe the EC-type examination certificate. | |
Relative humidity | 5 ... 95 % |
Degree of protection | IP20 | ||||||||||
Connection | screw terminals | ||||||||||
Core cross section | 2 x 2.5 mm2 | ||||||||||
Mass | approx. 100 g | ||||||||||
Dimensions | 12.5 x 115 x 116 mm (0.5 x 4.5 x 4.6 inch) (W x H x D) | ||||||||||
| |||||||||||
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
EU-type examination certificate | PTB 00 ATEX 2176 X | |||||||||||||||||||
| ||||||||||||||||||||
Certificate | PF 16 CERT 4065 X | |||||||||||||||||||
| ||||||||||||||||||||
Directive conformity | ||||||||||||||||||||
|
CSA approval | |||||
| |||||
IECEx approval | |||||
|
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |