选择您所在的国家/地区
KCD2-SCS-2.SP SMART Transmitter Power Supply/SMART Current Driver
主要优势一览
- 2-channel isolated barrier
- 24 V DC supply (Power Rail)
- Analog input (AI), Analog output (AO)
- Operates as transmitter power supply or current driver
- Housing width 12.5 mm
- Connection via spring terminals with push-in connection technology
- Up to SIL 2 (SC 3) acc. to IEC/EN 61508
显示详情


注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
DE
- DE
- EN
- ES
- FR
- PL
KCD2-SCS-2.SP 技术数据
Signal type | Analog input/analog output |
Safety Integrity Level (SIL) | SIL 2 | |
Systematic capability (SC) | SC 3 |
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | Ur | 19 ... 30 V DC |
Ripple | max. 10 % | |
Rated current | Ir | max. 88 mA at 24 V |
Power dissipation | max. 1.4 W | |
Power consumption | max. 2.1 W |
Number of channels | 2 | |
Suitable field devices | 2-wire SMART transmitters | |
Signal | 0/4 ... 20 mA , limited to approx. 30 mA | |
Field circuit | terminals 1+, 2-, 3+, 4- | |
Available voltage | min. 15 V at 20 mA min. 18 V at 4 mA | |
Control circuit | terminals 5-, 6+; 7-, 8+ | |
Input voltage | Voltage across terminals 10 ... 30 V. If the current is supplied from a source > 24 V, series resistance of ≥ (V - 24)/0.02 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 10)/0.02 Ω. (sink output) | |
Load | max. 350 Ω (source output) | |
Ripple | 20 mV eff |
Number of channels | 2 | |
Suitable field devices | SMART I/P converters (positioner), on-site-displays | |
Signal | 0/4 ... 20 mA , limited to approx. 30 mA | |
Field circuit | terminals 1+, 2-, 3+, 4- | |
Load | max. 650 Ω | |
Voltage | min. 13 V at 20 mA | |
Ripple | 20 mV eff , on all signal terminals | |
Control circuit | terminals 5-, 6+; 7-, 8+ | |
Voltage drop | max. 6 V | |
Line fault detection | > 100 kΩ at max. 30 V, with field wiring open |
Deviation | max. 20 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage | ||||
| |||||
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) | ||||
Settling time | max. 200 ms | ||||
Rise time/fall time | max. 100 ms (10 ... 90 %) |
Field circuit/control circuit | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Control circuit/control circuit | functional isolation, rated voltage: 50 V | |
Field circuit/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Control/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Display elements | LED | |
Factory setting | analog input with source output | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front |
Electromagnetic compatibility | |||||
|
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 | |
Degree of protection | IEC 60529:2001 |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Degree of protection | IP20 | ||||||||||
Connection | spring terminals | ||||||||||
Mass | approx. 115 g | ||||||||||
Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 | ||||||||||
| |||||||||||
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |