选择您所在的国家/地区

转至全球网站

HD2-DM-A Advanced Diagnostic ModuleFieldConnex® Fieldbus

主要优势一览

  • Comprehensive diagnostics for fieldbus physical layer and power supply
  • Plug-in Module for the FieldConnex Power Hub
  • Precise measurements through passive circuits
  • For commissioning, online monitoring and troubleshooting
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Installation in Zone 2/Class I, Div. 2
  • System state and fault indication via LEDs
  • Display of data in the safety of the control room
  • Automatic setup of diagnostic system
  • Full software integration into PCS and PAM possible

显示详情

FieldConnex® interface
Interface
Approval
Product Compliance: Europe – CE
FOUNDATION Fieldbus interface
PROFIBUS interface
注意

在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。

DE
  • DE
  • EN

HD2-DM-A 技术数据

Advanced diagnostic module, plug-in module for the fieldbus power hub
Design / MountingMotherboard based
Installation in hazardous areaZone 2 / Div. 2
Rated voltageUr19.2 ... 35 V
Rated currentIr110 ... 30 mA
Power dissipationmax. 2 W
Number of segments4
Fieldbus typeFOUNDATION Fieldbus/PROFIBUS PA
Rated voltageUN9 ... 32 V
LED PRI PWRgreen: on, primary bulk power supply connected
LED SEC PWRgreen: on, secondary bulk power supply connected
LED Seg 1...4yellow: bus activity; red 2 Hz flashing: alarm; red: hardware error
Fault signalVFC alarm 1 A, 50 V DC, normally closed
DIP switchdiagnostic address 1...247, binary coded
Interface typediagnostic bus: RS 485
Fieldbus segment/Fieldbus segmentfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Fieldbus segment/Supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Pollution degreemax. 2, according to IEC 60664
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Core cross sectionmotherboard specific
Housing materialPolycarbonate
Degree of protectionIP20
Massapprox. 100 g
Dimensions
Height106 mm
Width18 mm
Depth128 mm
Mountingmotherboard mounting
Mating cycles100
CertificateTÜV 04 ATEX 2500 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
FM approval
FM certificateFM 19 US 0015 X and FM 19 CA 0011 X
FM markingClass I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex ec IIC T4
IECEx approval
IECEx certificateIECEx TUN 13.0038X
IECEx markingEx nA IIC T4 Gc
PatentsThis product may be covered by the following patent: US7,698,103
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.