KFD2-EB2.R4A.B Redundant Power Feed Module
主要优势一览
- Interface for Power Rail
- Used for redundant configuration
- Supply current ≤ 4 A
- Replaceable fuse
- Relay contact output, reversible
- LED status indication
显示详情
首选类型



注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
DE
- DE
- EN
- ES
- FR
- PL
KFD2-EB2.R4A.B 技术数据
Power feed module, redundant supply |
Connection | terminals 11+, 12- terminals 8+, 9- | |
Rated voltage | Ur | 20 ... 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
Fusing | 5 AT/250 V AC recommended maximum utilization of the fuse: 80 % | |
Power dissipation | ≤ 2.4 W |
Connection | Power Rail | |
Output current | max. 4 A | |
Output voltage | Ui ≥ rated voltage Ur = Ui - 0.6 V | |
Fault signal | relay output: NO contact | |
Contact loading | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Display elements | LEDs | |
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front |
Electromagnetic compatibility | |||||
|
Electromagnetic compatibility | NE 21:2017 | |
Degree of protection | IEC 60529:2001 |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Certificate | UL 22 ATEX 2853 X | ||||
| |||||
Directive conformity | |||||
|
FM approval | FM 22 US 0031 X | |||||||
| ||||||||
UL approval | E106378 | |||||||
CSA approval | CoC 1051840 | |||||||
IECEx approval | ||||||||
|
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |