选择您所在的国家/地区

转至全球网站

HiDMux2700 HART Multiplexer

主要优势一览

  • 32-channel
  • 24 V DC supply
  • HART field device input (revision 5 to 7)
  • RS-485 interface
  • Up to SIL 3 acc. to IEC/EN 61508

显示详情

HART® interface
Approval
Product Compliance: USA - cCSAus
Functional Safety: Safety Integrity Level - 3
Product Compliance: Europe – CE
注意

在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。

DE
  • DE
  • EN
  • ES
  • FR
  • PL

HiDMux2700 技术数据

HART Multiplexer
Safety Integrity Level (SIL)SIL 3
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltageUr20.4 ... 30 V DC via Termination Board
Rated currentIr28 mA at 24 V , RS-485, quiescent current
Power dissipation0.7 W at 24 V
Number of channels32
ConformityHART field device input (revision 5 to 7)
Signal range0.12 Vpp < signal < 1.5 Vpp
Leakage current< 3 µA at -20 ... 85 °C (-4 ... 185 °F)
Terminating resistorexternal 230 ... 500 Ω standard (up to 1000 Ω possible)
Output voltage≥ 400 mV ss (with the terminator resistance specified above)
Output resistance100 Ω or smaller, capacitive coupling
DC isolationdual capacitor each channel
Common mode voltageup to 30 V
Input impedance> 5 kΩ , according to HART specification
Input voltage range0.12 ... 1.5 V ss
Common mode voltagemax. 30 V
Differential mode clamping± 5.2 V , for transient or AC signals
Common mode clamping± 10 V , for transient or AC signals
Carrier detect levelsignal > 0.12 Vpp, carrier detection activated
signal < 0.08 Vpp, carrier detection not activated
Transmit amplitude200 Ω load, 0.43 Vpp < signal < 0.49 Vpp
500 Ω load, 1.1 Vpp < signal < 1.2 Vpp
Device typeDC isolated bus device
Impedancehigh impedance
Data link typeHART primary and secondary
Field multi point supportoption available upon request
Transfer rate9600 MBit/s, 19200 MBit/s or 38400 MBit/s, selectable via switch
Address1 ... 31 , adjustable via DIP switch
TypeRS-485 , differential pair and grounding
Topologymulti point, primary module/secondary module connection
Interface/power supply500 Vrms
Interface/field channels1000 Veff
Power supply/field channels1000 Veff
Display elementsLEDs
LED PWR ON (power supply), one green LED
LED HART TX (HART transmission), one yellow LED
LED FAULT (lead fault), one red LED
Control elementsDIP switches at the housing side for:
- secondary module address
- baud rate
- test mode on/off
Configurationvia DIP switches
Labelingspace for labeling at the front
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Electromagnetic compatibilityNE 21:2012
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Relative humidity5 ... 95 %, noncondensing
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Mountingon termination board
CertificateCML 17 ATEX 3337X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018
CSA approval
CSA certificate1256050
Approved forClass I, Division 2, Groups A, B, C, D and non-explosion hazardous area
IECEx approval
IECEx certificateIECEx CML 17.0178X
IECEx markingEx ec IIC T4 Gc
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
一般说明