选择您所在的国家/地区
KFD2-GUT-Ex1.D Temperature Converter with Trip Values
主要优势一览
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- Thermocouple, RTD, potentiometer or voltage input
- Redundant TC input
- Current output 0/4 mA ... 20 mA
- 2 relay contact outputs
- Configurable by PACTware or keypad
- Line fault (LFD) and sensor burnout detection
- Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511
显示详情
首选类型



注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
DE
- DE
- EN
- ES
- FR
- PL
KFD2-GUT-Ex1.D 技术数据
Signal type | Analog input |
Safety Integrity Level (SIL) | SIL 2 |
Connection | terminals 23+, 24- or power feed module/Power Rail | |
Rated voltage | Ur | 20 ... 30 V DC |
Rated current | Ir | approx. 100 mA |
Power dissipation/power consumption | ≤ 2 W / 2.2 W |
Programming interface | programming socket |
Connection side | field side | ||||||||||
Connection | terminals 1, 2, 3, 4, 6 | ||||||||||
RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | ||||||||||
| |||||||||||
Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | ||||||||||
| |||||||||||
Potentiometer | 0.8 ... 20 kΩ | ||||||||||
| |||||||||||
Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | ||||||||||
Input resistance | ≥ 250 kΩ (0 ... 10 V) min. 1 MΩ (0 ... 1 V, -100 ... 100 mV) | ||||||||||
Measuring current | approx. 400 µA with resistance measuring sensor |
Connection side | control side | |||||||||||||
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |||||||||||||
Output I, II | relay | |||||||||||||
| ||||||||||||||
Output III | Analog current output | |||||||||||||
| ||||||||||||||
Collective error message | Power Rail |
Deviation | ||||||||||||||||||||
| ||||||||||||||||||||
Sampling rate | approx. 700 ms |
Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output III/power supply and collective error | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front |
Electromagnetic compatibility | |||||
| |||||
Low voltage | |||||
|
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 | ||||||||||
Connection | screw terminals | ||||||||||
Mass | 300 g | ||||||||||
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | ||||||||||
| |||||||||||
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
EU-type examination certificate | TÜV 03 ATEX 2140 | |||||||||||||||||||
| ||||||||||||||||||||
Supply | ||||||||||||||||||||
| ||||||||||||||||||||
Input | terminals 2, 6 (for active equipment) | |||||||||||||||||||
| ||||||||||||||||||||
Inputs | terminals 1, 2, 3, 4, 6 (for passive equipment) | |||||||||||||||||||
| ||||||||||||||||||||
Analog output | ||||||||||||||||||||
| ||||||||||||||||||||
Interface | ||||||||||||||||||||
| ||||||||||||||||||||
Certificate | PF 08 CERT 1213 X | |||||||||||||||||||
| ||||||||||||||||||||
Output I, II | ||||||||||||||||||||
| ||||||||||||||||||||
Galvanic isolation | ||||||||||||||||||||
| ||||||||||||||||||||
Directive conformity | ||||||||||||||||||||
|
IECEx approval | ||||||||
|
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |