选择您所在的国家/地区
F2-SP-IC* Segment ProtectorFieldConnex® Fieldbus
主要优势一览
- 4 ... 10 outputs Ex ic (FISCO or Entity)
- Advanced fault isolation at the spur
- Segment Protector in Zone 2
- Instruments in Zone 2 or Zone 1
- For FOUNDATION Fieldbus H1 and PROFIBUS PA
- Advanced Diagnostics at the spur
- Power, Com, Terminator, Diagnostics, and Error LEDs
显示详情


注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
DE
- DE
- EN
F2-SP-IC* 技术数据
Segment protector, junction box for fieldbus with short-circuit and fault protection, field junction box, stand-alone device in aluminum housing for field installation |
Design / Mounting | Outside installation | |
Installation in hazardous area | Zone 2 / Div. 2 |
Main cable (Trunk) | ||||||||||||||||||||
| ||||||||||||||||||||
Outputs | ||||||||||||||||||||
| ||||||||||||||||||||
Self current consumption | see table "Technical data depending on model" | |||||||||||||||||||
Voltage drop main cable/outputs | max. 1.2 V | |||||||||||||||||||
Voltage drop trunk In/Out | 0 V | |||||||||||||||||||
Terminating resistor | selectable via Jumper 100 Ω +/- 10 % | |||||||||||||||||||
Surge protection | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V |
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated | |
LED PWR/TERM | green: Fieldbus voltage > 10 V and fieldbus terminator is activated | |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status | |
LED SPURS | red: 2 Hz flashing in short-circuit condition | |
Jumper 1 | configuration of short-circuit current/rated current | |
Jumper 2 | configuration of grounding option for trunk and cable screen/shield |
Electromagnetic compatibility | |||||
|
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 |
Ambient temperature | see table 2 | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Connection type | screw terminal , fixed screw terminal , pluggable spring terminal | |
Core cross section | max. 2.5 mm2 /AWG 12-24 | |
Cable diameter | see table 3 | |
Housing | see figure 1 | |
Housing material | Aluminum | |
Degree of protection | IP66 | |
Mass | max 2.6 kg , depending on model | |
Dimensions | see table 2 | |
Mounting | wall mounting |
EU-type examination certificate | TÜV 13 ATEX 107689 X | |||||||||||||
| ||||||||||||||
Supply | ||||||||||||||
| ||||||||||||||
Outputs | ||||||||||||||
| ||||||||||||||
Directive conformity | ||||||||||||||
|
IECEx approval | ||||||||
|
FOUNDATION Fieldbus | FF-846 |
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |