KFD2-HLC-Ex1.D HART Loop Converter
主要优势一览
- 1-channel isolated barrier
- 24 V DC supply (Power Rail)
- HART field device input with transmitter power supply
- Usable as signal splitter (1 input and several outputs)
- 3 analog outputs 4 mA ... 20 mA
- Sink and source mode output
- Configurable by keypad
显示详情


注意
在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。
DE
- DE
- EN
- ES
- FR
- PL
KFD2-HLC-Ex1.D 技术数据
Signal type | Analog input |
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | Ur | 19 ... 30 V DC |
Rated current | Ir | approx. 120 mA at 24 V DC |
Power dissipation | 2.3 W | |
Power consumption | 2.9 W |
Conformity | HART field device input (revision 5 to 7) |
Programming interface | programming socket |
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | ≥ 15.5 V at 20 mA, short-circuit protected |
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 | |
Output signal | analog | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Current range | 4 ... 20 mA , (source or sink mode) | |
Load | max. 650 Ω , source mode | |
Fault signal | downscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red |
Output I, II, III | ||||||||||||||
|
Output I/II/III/power supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front |
Electromagnetic compatibility | |||||
| |||||
Low voltage | |||||
|
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Degree of protection | IP20 | ||||||||||
Connection | screw terminals | ||||||||||
Mass | 300 g | ||||||||||
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | ||||||||||
| |||||||||||
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
EU-type examination certificate | BASEEFA 07 ATEX 0174 | ||||||||||||||||||||||
| |||||||||||||||||||||||
Supply | |||||||||||||||||||||||
| |||||||||||||||||||||||
Equipment | terminals 1, 4/3 (with link between terminals 4 and 5) | ||||||||||||||||||||||
| |||||||||||||||||||||||
Equipment | terminals 2, 5/3 | ||||||||||||||||||||||
| |||||||||||||||||||||||
Output I, II, III | terminals 7, 8, 9; 13, 14, 15; 19, 20, 21 non-intrinsically safe | ||||||||||||||||||||||
| |||||||||||||||||||||||
Certificate | PF 07 CERT 1142 X | ||||||||||||||||||||||
| |||||||||||||||||||||||
Galvanic isolation | |||||||||||||||||||||||
| |||||||||||||||||||||||
Directive conformity | |||||||||||||||||||||||
|
FM approval | ||||||||
| ||||||||
IECEx approval | ||||||||
|
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |