选择您所在的国家/地区

转至全球网站

S1SD-1TI-1U Temperature Converter

主要优势一览

  • 1-channel signal conditioner
  • 24 V DC supply
  • Thermocouple, RTD, potentiometer or mV input
  • Input for PTC thermistor
  • Current and voltage output
  • Line fault (LFD) and sensor burnout detection
  • Accuracy 0.1 %
  • Connection via screw terminals

显示详情

Approval
Product Compliance: Europe – CE
Approval
Product Compliance: USA - cULus
注意

在转换前以倍加福有限公司或倍加福股份公司名义发布的所有产品文档(如证书、符合性声明等)也适用于倍加福欧洲公司。

DE
  • DE
  • EN
  • ES
  • FR
  • PL

S1SD-1TI-1U 技术数据

Signal typeAnalog input
Operation timeMTBF: 353 a acc. to SN 29500
stationary continuous operating, average ambient temperature 40 °C (104 °F)
ConnectionPower Bus or terminals 1-, 2+
Rated voltageUr16.8 ... 31.2 V DC
Power dissipation0.7 W
Power consumption0.8 W
Programming interfaceprogramming socket
Connection sidefield side
Connectionterminals 5, 6, 7, 8
PTCtype KT, KTY, ST
Measuring currentapprox. 200 µA
Types of measuring2-, 3-, 4-wire connection
Lead resistance≤ 100 Ω per line
Measurement loop monitoringsensor breakage, lead breakage, short circuit
RTDtype Pt100, Pt200, Pt500, Pt1000 (EN 60751:1995)
type Ni100, Ni200, Ni500, Ni1000 (DIN 43760)
Measuring currentapprox. 200 µA
Types of measuring2-, 3-, 4-wire connection
Lead resistancemax. 100 Ω per line
Measurement loop monitoringsensor breakage, lead breakage, short circuit
Thermocouplestype B, E, J, K, N, S, T (IEC 584-1:1995)
type L, U (DIN 43710:1985)
type C, D (ASTM E988)
Cold junction compensationexternal (Pt100) and internal , manually
Lead resistancemax. 10 kΩ
Measurement loop monitoringsensor breakage, lead breakage
Resistor
Measuring range0 ... 5 kΩ
Potentiometer0.2 ... 50 kΩ
Types of measuring3-wire connection
Voltage-100 ... 100 mV
-1000 ... 1000 mV
Input resistance≥ 1 MΩ
Connection sidecontrol side
Connectionterminals 3-, 4+
Analog voltage output0/1 ... 5 V , 0/2 ... 10 V , load ≥ 2 kΩ
Analog current output0/2 ... 10 mA, 0/4 ... 20 mA, load ≤ 600 Ω
Ripple≤ 10 mV eff
Fault signaldownscale or upscale
Accuracymax. 0.1 % of full-scale value
Measuring time≤ 300 ms
Deviation
RTD< 0.1 K/0.05 % of the measured value
Thermocouples< 0.3 K/0.1 % of the measured value
Voltage< 0.1 % of the measured value
Potentiometer< 0.02 % of the measured value
Influence of ambient temperature< 100 ppm/K of full-scale value
Output/power supplysafe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min
Input/Other circuitssafe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min
Control elementsDIP switch
keys
Configurationvia DIP switches
via keys
via software
Labelingspace for labeling at the front
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Degree of protectionIEC 60529:2001
Protection against electrical shockEN 61010-1:2010
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Degree of protectionIP20
Connectionscrew terminals
Core cross section0.5 ... 2.5 mm2 (20 ... 14 AWG)
Massapprox. 70 g
Dimensions6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1
Height97 mm
Width6.2 mm
Depth107 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
CertificateDEMKO 16 ATEX 1750X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-15:2010
UL approvalE106378
IECEx approval
IECEx certificateIECEx UL 16.0116X
IECEx markingEx nA IIC T4 Gc
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
一般说明