General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 19 ... 90 V DC / 48 ... 253 V AC | |
Rated current | ≤ 110 mA DC / ≤ 75 mA AC | |
Power dissipation | 1.3 W | |
Power consumption | 2.1 W | |
Input | ||
Connection side | field side | |
Input I | ||
Connection | terminals 1+, 2-, 3 | |
Input signal | 0/4 ... 20 mA | |
Rated current | 22 mA | |
Available voltage | > 15 V at 20 mA , terminals 1+, 3- | |
Open circuit voltage/short-circuit current | 21 V / 26 mA , terminals 1+, 3- terminals 1+, 2- not short-circuit protected |
|
Input resistance | < 55 Ω , terminals 2-, 3+ | |
Input II | ||
Connection | terminals 5-, 6+ | |
Input signal | 0/2 ... 10 V | |
Input resistance | > 1 MΩ | |
Output | ||
Connection side | control side | |
Output I | current output | |
Connection | source: terminals 7(-), 8(+) sink: terminals 7(+), 9(-) |
|
Output signal | 0/4 ... 20 mA | |
Source | load 0 ... 750 Ω open circuit voltage < 21 V | |
Sink | voltage across terminals 5 ... 30 V | |
Output II | voltage output | |
Connection | terminals 10-, 11+ | |
Output signal | 0/2 ... 10 V | |
Load | min. 10 kΩ | |
Transfer characteristics | ||
Deviation | ||
Resolution/accuracy | S1 in position I: 7 µA/40 µA (0.2 %) S1 in position II: 3.5 mV/20 mV (0.2 %) |
|
Influence of ambient temperature | 0.01 % / K of output signal range | |
Reaction time | 150 ms | |
Galvanic isolation | ||
Input/Output | functional insulation acc. to IEC 62103, rated insulation voltage 100 Vrms | |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP switch rotary switch |
|
Configuration | via DIP switches via rotary switch |
|
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:1989+A1:1999+A2:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Height | 119 mm | |
Width | 20 mm | |
Depth | 115 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210119 |
ECLASS 12.0 | 27210119 |
ECLASS 11.0 | 27210119 |
ECLASS 10.0.1 | 27210119 |
ECLASS 9.0 | 27210119 |
ECLASS 8.0 | 27210119 |
ECLASS 5.1 | 27210119 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
This signal conditioner provides the isolation for non-intrinsically safe applications.
The device supplies 2-wire and 3-wire transmitters, and can also be used with current and voltage sources.
The input ranges include 0/4 mA ... 20 mA or 0/2 V ... 10 V.
At the output the signal is available as 0/4 mA ... 20 mA or 0/2 V ... 10 V.
Output and measuring range are selected by switches located on the front of the device.
Literature | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation Stage | ENG | 566 KB | |
Application Report - Generating Electricity in Coal-Fired Power Plants | ENG | 412 KB | |
Application Report - Sand Trap and Preliminary Sedimentation Stage | ENG | 448 KB | |
Application Report - Screening Systems in Sewage Treatment Plants | ENG | 577 KB |
Safety and Security Documentation | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Instrukcja obsługi | POL | 57 KB | |
Manuals | |||
System Manual | ENG | 3694 KB |
CAD | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2510 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 63 KB |
Declaration of Conformity | Nr. certyfikatu | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|---|
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-3179A | ALL | 373 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
Accessories | ||||||
|
||||||
|