General specifications | ||
---|---|---|
Number of protected signal lines | 1 | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | ≤ 48 V | |
Rated current | ≤ 250 mA | |
Leakage current | ≤ 5 µA | |
On-state voltage | ≤ 85 V | |
Ground insulation | ≥ 500 V breakdown voltage | |
Electrical specifications | ||
Total discharge current (8/20 µs) | 20 kA | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -30 ... 60 °C (-22 ... 140 °F) For usage in hazardous area observe the EC-type examination certificate. | |
Mechanical specifications | ||
Housing material | Stainless steel 1.4401 (AISI 316) surface all over polished |
|
Degree of protection | IP67 | |
Cable | ||
Length | 0.3 m | |
Mass | approx. 200 g | |
Dimensions | AF22 x 77 mm (0.9 x 3 inch) | |
Length | 77 mm | |
Width across flats | 22 | |
Mounting | NPT1/2 thread | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 00 ATEX 2175 | |
Marking | II 2G EEx ia IIC T6 | |
Voltage | 50 V | |
Maximum leakage current | 10 kA line to ground (common), 5 kA line to line (differential) in accordance to IEC 60-2 | |
Nominal response time | ||
Symmetrical | 1 ns | |
Asymmetric | 100 ns | |
Bandwidth | ≥ 40 kHz | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0187 (cCSAus) | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27171202 |
ECLASS 12.0 | 27171202 |
ECLASS 11.0 | 27130805 |
ECLASS 10.0.1 | 27130805 |
ECLASS 9.0 | 27130805 |
ECLASS 8.0 | 27130805 |
ECLASS 5.1 | 27130801 |
ETIM 9.0 | EC000941 |
ETIM 8.0 | EC000941 |
ETIM 7.0 | EC000941 |
ETIM 6.0 | EC000941 |
ETIM 5.0 | EC000941 |
UNSPSC 12.1 | 39121610 |
This Surge Protection Barrier limits induced transients of different origin (e. g. lightning stroke, switching impulse, etc.). This is achieved by diverting the transient current to ground and limiting the signal line voltage to a safe level for the duration of the surge.
This barrier provides 85 V line-to-line and 500 V line-to-ground clamping voltage for the protected instruments. It also protects instruments that have less than 500 V isolation-to-ground.
It is installed in an available conduit or cable gland opening like those found on most process transmitters.
For additional information, refer to the manual and www.pepperl-fuchs.com.
Note: Surge Protection Barriers must always be connected to a solid and effective ground and be at the same equipotential level as the instrument it is protecting. The ground system must comply with all applicable regulations.
Safety and Security Documentation | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Instrukcja obsługi | POL | 154 KB | |
Manual | ENG | 2244 KB | |
Manuals | |||
Brief Instructions - Surge Protection Barriers | ENG | 876 KB | |
Manual P-LB,F-LB,K-LB | ENG | 1151 KB |
CAD | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 102 KB |
Certificates | Nr. certyfikatu | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|---|
Canada, USA CSA | CoC 1128189 | ALL | 62 KB | |
China SITIIAS CCC Ex Certificate | 2020322304002781 (Singapore) | ALL | 870 KB | |
Europe PTB ATEX Category 2 G | PTB 00 ATEX 2175 | ALL | 353 KB | |
exida Functional Safety Assessment | P+F 11-10-085 R036 V1R0 | ALL | 477 KB | |
Control Drawings | ||||
Control drawing CSA / Control drawing CSA | ALL | 179 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0969A | ALL | 88 KB |