Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem

Bullet WirelessHART Adapter WHA-BLT-F9D0-N-A0-GP-1

WHA-BLT-F9D0-N-A0-GP-1
  • Cast aluminum housing
  • Loop powered
  • Direct mounting on HART or 4 mA ... 20 mA field device
  • Encapsulated antenna
  • Up to 8 field devices in multidrop

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  WHA-BLT-F9D0-N-A0-GP-1

Supply
Rated voltage7 ... 32 V DC
Rated current< 1 mA , max. 25 mA
Electrical specifications
Output current3.2 ... 25 mA
Supplyloop power for field devices
voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V
Input
Connection- 5 wires, 600 mm long, exiting from male thread NPT1/2
- 1 external grounding point
HART communication
ProtocolHART 7.1, backward compatible
Number of devicesup to 8 HART field devices (depending on installation)
Output
Interfaceinternal antenna
CommunicationWirelessHART specifications
- physical layer: IEEE 802.15.4.2006
- frequency band: 2.4 GHz (ISM band, licence free)
- maximum transmit power: +10 dBm
- outdoor transmission range: 235 m
- communication standard: WirelessHART acc. to IEC 62591
Directive conformity
Radio and telecommunication terminal equipmentThe usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning.
Directive 2014/53/EUEN 300 328 V2.1.1:2016
EN 301 489-1 V2.2.0:2017
EN 301 489-17 V3.2.0:2017
FCC CFR47 Part 15 B and CANSI C63.4-2003 , FCC ID: X89-WA1101
Conformity
Degree of protectionIEC 60529:2013
Ambient conditions
Ambient temperature-40 ... 85 °C (-40 ... 185 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 100 %
Mechanical specifications
Degree of protectionIP67
Materialaluminum alloy with polyurethane enamel paint
Mass460 g
Dimensions60.8 x 60.8 x 100 mm (l x w x h)
Height100 mm
Diameter60.8 mm
International approvals
FM approvalFM 17 NUS 0010
Control drawing116-0425 (cFMus)
CSA approvalFM 17 NCA 0004
Control drawing116-0425 (cFMus)
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027219090
ECLASS 12.027219090
ECLASS 11.027219290
ECLASS 10.0.127219290
ECLASS 9.027219290
ECLASS 8.027219290
ECLASS 5.127242692
ETIM 9.0EC002584
ETIM 8.0EC002584
ETIM 7.0EC002584
ETIM 6.0EC002584
ETIM 5.0EC002584
UNSPSC 12.139121008

Details: WHA-BLT-F9D0-N-A0-GP-1

Function

The device upgrades a conventional HART or 4 ... 20 mA field device with a WirelessHART interface.

The supply is ensured via loop power. The adapter is suitable for use in a nonhazardous area and it can be used directly on the field device or it can be integrated in the 4 ... 20 mA loop. Up to 8 HART field devices can be connected to each other in multidrop mode.

The device can be programmed with a configuration tool easily (DTM or DD).

Informative Literature: WHA-BLT-F9D0-N-A0-GP-1

Language Selection:
LiteratureJęzykTyp plikuRozmiar pliku
Application Report - Outdoor Monitoring of Gas Limit ValuesENGPDF158 KB
Application Report - WirelessHART Adapter Bullet Enables More Flexibility for Mobile Mixing TanksENGPDF129 KB
Application Report - WirelessHART Connects Mobile Measurement StationsENGPDF149 KB
Application Report - Wirelessly Networked Tank FarmsENGPDF736 KB

Product Documentation: WHA-BLT-F9D0-N-A0-GP-1

Language Selection:
System DescriptionsJęzykTyp plikuRozmiar pliku
Patent InformationENGPDF365 KB
Safety and Security Documentation
Instrukcja obsługiPOLPDF120 KB
Manuals
ManualENGPDF2085 KB

Approvals: WHA-BLT-F9D0-N-A0-GP-1

Language Selection:
Control DrawingsNr. certyfikatuJęzykTyp plikuRozmiar pliku
Control drawing CSA / Control drawing CSA   ALLPDF187 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3837CALLPDF73 KB

Software: WHA-BLT-F9D0-N-A0-GP-1

Language Selection:
Device Description Files/DriversInformacja o wersjiTyp plikuRozmiar pliku
DTM WirelessHART Adapter WHA-BLT* "Bullet" / DTM WirelessHART Adapter WHA-BLT* "Bullet"ZIP16481 KB
FHX-File WirelessHART Adapter WHA-BLT* "Bullet" / FHX-Datei WirelessHART Adapter WHA-BLT* "Bullet"ZIP1115 KB
DD WirelessHART Adapter WHA-BLT* "Bullet" / DD WirelessHART Adapter WHA-BLT* "Bullet"ZIP3513 KB

Produkty powiązane: WHA-BLT-F9D0-N-A0-GP-1

Accessories
Device DTMpa
Adapter male thread metric to female thread metric, Adapter male thread metric to female thread NPT, Metric and NPT versions available, Brass nickel-plated or stainless steel, Ex db, Ex eb and Ex tb certified, Suitable for operation in Zone 1, Zone 2, Zone 21 and Zone 22pa