General specifications |
Signal type | Digital Input |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 20 ... 30 V DC |
Rated current | 30 ... 40 mA |
Input |
Connection side | field side |
Connection | terminals 1, 4 (mass), 2, 5 (min), 3, 6 (max) |
Control input | min./max. control system: terminals 1, 2, 3; 4, 5. 6 on/off control system: terminals 1, 3; 4, 6 |
Response sensitivity | 1 ... 150 kΩ , adjustable via potentiometer |
Output |
Connection side | control side |
Connection | terminals 7, 8, 9; 10, 11, 12 |
Switching power | max. 192 W , 2000 VA |
Output | relay |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Time constant for signal damping | 0.5 s, 2 s, 5 s, 10 s |
Galvanic isolation |
Input/Output | basic insulation according to EN 50178, rated insulation voltage 253 Veff |
Input/power supply | basic insulation according to EN 50178, rated insulation voltage 253 Veff |
Output/power supply | basic insulation according to EN 50178, rated insulation voltage 253 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP switch potentiometer |
Configuration | via DIP switches via potentiometer |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2004/108/EC | EN 61326-1:2006 |
Low voltage | |
| Directive 2006/95/EC | EN 50178:1997 |
Conformity |
Insulation coordination | EN 50178:1997 |
Galvanic isolation | EN 50178:1997 |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals , max. 2.5 mm2 |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Width | 20 mm |
| Depth | 115 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |