General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC | |
Power dissipation | 2 W / 3 VA | |
Power consumption | 2.2 W / 4 VA | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Available voltage | > 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 Ω (terminals 2, 3) | |
Line fault detection | breakage I < 0.2 mA; short-circuit I > 22 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- |
|
Output signal | 0 ... 20 mA or 4 ... 20 mA | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Output III | Signal, analog | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 Ω | |
Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) | |
Energized/De-energized delay | 0 ... 250 s , adjustable | |
Transfer characteristics | ||
Input I | ||
Accuracy | < 30 µA | |
Influence of ambient temperature | 0.003 %/K (30 ppm) | |
Output I, II | ||
Response delay | ≤ 200 ms at bounce from 0 ... 20 mA | |
Output III | ||
Resolution | ≤ 10 µA | |
Accuracy | < 20 µA | |
Influence of ambient temperature | 0.005 %/K (50 ppm) | |
Reaction time | < 650 ms at bounce from 0 ... 20 mA at the input, 90 % of output full-scale value | |
Galvanic isolation | ||
Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output III/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware |
|
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | |
Height | 119 mm | |
Width | 40 mm | |
Depth | 115 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | TÜV 01 ATEX 1701 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Input | Ex ia | |
Supply | ||
Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) | |
Equipment | terminals 1+, 3- | |
Voltage | 25.8 V | |
Current | 93 mA | |
Power | 0.603 W | |
Equipment | terminals 2-, 3 | |
Voltage | < 30 V | |
Current | 115 mA | |
Voltage | 5 V | |
Current | 0.3 mA | |
Power | 0.3 mW | |
Equipment | terminals 1+, 2 / 3- | |
Voltage | 25.8 V | |
Current | 112 mA | |
Power | 720 mW | |
Output I, II | terminals 10, 11, 12; 16, 17, 18 non-intrinsically safe | |
Maximum safe voltage | 253 V AC / 40 V DC (Attention! Um is no rated voltage.) | |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 01 ATEX 1701) |
|
Output III | terminals 8+, 7- non-intrinsically safe | |
Maximum safe voltage | 40 V (Attention! The rated voltage can be lower.) | |
Interface | RS 232 | |
Maximum safe voltage | 40 V (Attention! The rated voltage can be lower.) , RS 232 | |
Galvanic isolation | ||
Input/Other circuits | safe galvanic isolation acc. to EN 50020, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
International approvals | ||
FM approval | ||
Control drawing | 16-554FM-12 (cFMus) | |
IECEx approval | ||
IECEx certificate | IECEx TUN 09.0007 | |
IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210119 |
ECLASS 12.0 | 27210119 |
ECLASS 11.0 | 27210119 |
ECLASS 10.0.1 | 27210119 |
ECLASS 9.0 | 27210119 |
ECLASS 8.0 | 27210119 |
ECLASS 5.1 | 27210119 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire and 3-wire transmitters, and can also be used with current sources.
Two relays and an active 0/4 mA to 20 mA current source are available as outputs. The relay contacts and the current output can be integrated in safety-relevant circuits. The current output is easily scaled.
On the display the measured value can be indicated in various physical units.
The device is easily configured by the use of keypad or with the PACTware configuration software.
The input has a line fault detection.
A fault is signalized by LEDs.
For additional information, refer to the manual and www.pepperl-fuchs.com.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation Stage | ENG | 566 KB | |
Application Report - Energy Generation in Wastwater Treatment Plants | ENG | 532 KB | |
Application Report - Generating Electricity in Coal-Fired Power Plants | ENG | 412 KB | |
Application Report - Sand Trap and Preliminary Sedimentation Stage | ENG | 448 KB | |
Application Report - Screening Systems in Sewage Treatment Plants | ENG | 577 KB | |
Application Report - Sicherer Brennstofftransport in Kohlekraftwerken | ENG | 391 KB | |
Application Report - Water Inlet in Wastewater Treatment Plants | ENG | 526 KB |
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Operator card KF**-CRG2-**1.D / Bedienkarte KF**-CRG2-**1.D | ALL | 758 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 163 KB | |
Functional Safety Manual | ENG | 1936 KB | |
Manuals | |||
Manual | ENG | 2313 KB | |
Manual | ENG | 3685 KB | |
Installation and configuration guide Device Type Manager (DTM) | ENG | 8665 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2719 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 2070 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Australia Test Safe | ANZEx 17.3006X | ALL | 6788 KB | |
Brasil TUV Rheinland Brazil | TÜV 13.1155 | ALL | 1234 KB | |
Canada FM | FM22CA0015X | ALL | 355 KB | |
China SITIIAS CCC Ex Certificate | 2020322316001445 (Singapore) | ALL | 1321 KB | |
DNV Marine | TAA00001WX | ALL | 106 KB | |
Europe TUV Nord ATEX Category (1) D ATEX Category (M1) ATEX Category (1) G | TÜV 01 ATEX 1701 | ALL | 577 KB | |
Korea KOSHA | 14-AV4BO-0162 | ALL | 284 KB | |
PESO (India) CCOE | A/P/HQ/KA/104/5800 (P483619) | ALL | 80 KB | |
South Africa MASC | MASC MS/17-0879 | ALL | 736 KB | |
TUV Nord IECEx Certificate of Conformity | IECEx TUN 09.0007 | ALL | LINK | --- |
USA FM | CoC 3033495 | ALL | 38 KB | |
United Arab Emirates SGS Gulf Limited ECASEx | 23-12-96802/E23-12-099926/NB0002 | ALL | 602 KB | |
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1) | CML 22UKEX2503X | ALL | 154 KB | |
Control Drawings | ||||
Control drawing FM / Control drawing FM | ALL | 153 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2754B | ALL | 52 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 2 | 1.4.110.77 | ZIP | --- |
Software Tools | |||
PACTware 4.1 SP6 / PACTware 4.1 SP6 | 4.1.0.53 | ZIP | 43327 KB |
PACTware 5.0 / PACTware 5.0 | 5.0.5.31 | ZIP | 44203 KB |
PACTware 6.X / PACTware 6.X | 6.1 | ZIP | 335938 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|
||||||
|
||||||
|