General specifications |
Signal type | Digital Output |
Supply |
Rated voltage | loop powered |
Power dissipation | < 2 W |
Power consumption | |
Input |
Connection side | control side |
Connection | terminals 5+, 6-; 7+, 8- limited electrical values : max. 30 V , max. 5 A |
Test pulse length | max. 2 ms from DO card |
Signal level | 1-signal: 18 ... 30 V DC 0-signal: 0 ... 5 V DC |
Rated voltage | 18 ... 30 V DC |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 20 mA (minimum load current DO card) |
Inrush current | ≤ 200 mA after 100 µs |
Output |
Connection side | field side |
Connection | terminals 1+, 2-; 3+, 4- |
Internal resistor | approx. 167 Ω |
Current | typ. 45 mA |
Voltage | ≥ 15 V |
Current limit | 45 mA |
Open loop voltage | typ. 23.8 V |
Switching frequency | max. 10 Hz |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Galvanic isolation |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LED |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2017 , EN IEC 61326-1:2021 (industrial locations) , EN IEC 61326-3-2:2018 For further information see system description. |
Degree of protection | IEC 60529:2013 |
Protection against electrical shock | UL 61010-1:2019 |
Ambient conditions |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 95 g |
Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 |
| Height | 119 mm |
| Width | 12.5 mm |
| Depth | 114 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | UL 23 ATEX 3027 X |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Output | Ex ia Refer to certificate for alternative parameters. |
| Voltage | 25.3 V |
| Current | 52 mA |
| Power | 850 mW (angular characteristic curve) |
| Internal resistance | 167 Ω |
Input | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Certificate | UL 23 ATEX 3065 X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals |
UL approval | E106378 |
| Control drawing | 116-0496 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx ULD 23.0016X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |