Atendimento ao Cliente da Divisão de Sensores Industriais
Rede de Atendimento - Divisão de Proteção Contra Explosão

Solenoid Driver KFD2-SL2-Ex2

KFD2-SL2-Ex2
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Output 45 mA at 11.7 V DC
  • Logic input, non-polarized
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Faça o download das folhas de dados em PDF:


Folhas de dados: Dados técnicos do  KFD2-SL2-Ex2

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Power consumptionmax. 3.3 W at 45 mA output current
Input
Connection sidecontrol side
Connectionterminals 7, 8, 9
Input currentapprox. 3 mA at 24 V DC
Signal level1-signal: 16 ... 30 V DC
0-signal: 0 ... 5 V DC
Output
Connection sidefield side
Connectionchannel 1: terminals 1+, 2-, 3
channel 2: terminals 4+, 5-, 6-
Internal resistor272 Ω
Current≤ 45 mA
Voltage≥ 11.7 V
Current limit45 mA
Open loop voltagemin. 24 V
Output signalThese values are valid for the rated operating voltages from 20 ... 30 V DC.
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Line fault detection
Short-circuit< 50 Ω
Open-circuit> 10 kΩ
Test current< 650 µA
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Power supply/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 50 °C (-4 ... 122 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateZELM 00 ATEX 0024
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Voltage28 V
Current110 mA
Power770 mW (linear characteristic)
Supply
Maximum safe voltage40 V (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Collective error message
Maximum safe voltage40 V (Attention! The rated voltage can be lower.)
CertificateTÜV 02 ATEX 1820 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
International approvals
CSA approval
Control drawing116-0304
IECEx approval
IECEx certificateIECEx TUN 04.0001
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KFD2-SL2-Ex2

Product Documentation: KFD2-SL2-Ex2

Selecione o Idioma:
Product informationIdiomaTipo de ArquivoTamanho do Arquivo
Application Guideline Solenoid DriversENGPDF734 KB
Safety and Security Documentation
Manual de instruçõesPORPDF165 KB
Functional Safety ManualENGPDF486 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-SL2-Ex2

Selecione o Idioma:
CADIdiomaTipo de ArquivoTamanho do Arquivo
CAD 3-D / CAD 3-DALLSTP2308 KB

Approvals: KFD2-SL2-Ex2

Selecione o Idioma:
CertificatesNúmero do CertificadoIdiomaTipo de ArquivoTamanho do Arquivo
Australia Test SafeANZEx 17.3006XALLPDF6788 KB
Canada FMCoC 3028768CALLPDF316 KB
China SITIIAS CCC Ex Certificate2020322316001447 (Singapore)ALLPDF1077 KB
DNV MarineTAA00001WXALLPDF106 KB
Europe TUV Nord ATEX Category 3 GTÜV 02 ATEX 1820XALLPDF1397 KB
Europe ZELM ATEX Category (1) GD ATEX Category (M1)ZELM 00 ATEX 0024ALLPDF1157 KB
India PESO (India) CCOEA/P/HQ/KA/104/5851 (P502033)ALLPDF100 KB
Korea KOSHA12-AV4BO-0645ALLPDF850 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0001ALLLINK---
USA FMCoC 3028768ALLPDF296 KB
Ukraine SERTIS ExSC 21.0646 XALLPDF12351 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 21UKEX2935ALLPDF141 KB
exida Functional Safety AssessmentP+F 06/09-23 R029ALLPDF565 KB
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF108 KB
Declaration of Conformity
Declaração de conformidade UETDOC-0059FPORPORPDF152 KB

Produtos Relacionados: KFD2-SL2-Ex2

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector