Atendimento ao Cliente da Divisão de Sensores Industriais
Rede de Atendimento - Divisão de Proteção Contra Explosão

Standstill and Rotational Direction Monitor KFD2-SR2-Ex2.W.SM

KFD2-SR2-Ex2.W.SM
  • 2-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Dry contact or NAMUR inputs
  • Selectable frequency trip values
  • 2 relay contact outputs
  • Start-up override
  • Selectable mode of operation
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Faça o download das folhas de dados em PDF:


Folhas de dados: Dados técnicos do  KFD2-SR2-Ex2.W.SM

General specifications
Signal typeDigital Input
Programmingvia DIP switch and programmable
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage20 ... 30 V DC
Power consumptionmax. 1.5 W
Input
Connection sidefield side
ConnectionInput I: terminals 1+, 2+, 3- ;
Input II: terminals 4+, 5+, 6-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I > 6 mA
Control inputsensor power supply approx. 8.2 V, impedance 1.2 kΩ
Pulse duration> 200 µs for standstill monitoring,
> 250 µs for rotation direction detecion
Output
Connection sidecontrol side
Connectionoutput I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
Contact loading250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load
Minimum switch current2 mA / 24 V DC
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Mechanical life107 switching cycles
Trip valuefor standstill monitoring:
0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz
adjustable via DIP switch (S1 and S2)
Transfer characteristics
Accuracy5 % (S3 = I), 30 % (S3 = II)
Start-up override5 seconds or 20 seconds, programmable
Frequency range≤ 2 kHz
Rotation direction detection90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2080
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Voltage10.5 V
Current13 mA
Power34 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Fault indication output
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
CertificateTÜV 99 ATEX 1493 X
MarkingEx-Hexagon II 3G Ex ec nC IIC T4 Gc
Output
Contact loading50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
International approvals
FM approval
FM certificateFM19US0207X
Control drawing116-0035
UL approvalE106378
Control drawing116-0145
Contact loading250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load
CSA approval
Control drawing116-0047
IECEx approval
IECEx certificateIECEx PTB 11.0034 , IECEx TUN 19.0013X
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex ec nC IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210128
ECLASS 12.027210128
ECLASS 11.027210128
ECLASS 10.0.127210128
ECLASS 9.027210128
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC002918
ETIM 8.0EC002918
ETIM 7.0EC002918
ETIM 6.0EC002918
ETIM 5.0EC002475
UNSPSC 12.139121007

Details: KFD2-SR2-Ex2.W.SM

Informative Literature: KFD2-SR2-Ex2.W.SM

Selecione o Idioma:
LiteratureIdiomaTipo de ArquivoTamanho do Arquivo
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFD2-SR2-Ex2.W.SM

Selecione o Idioma:
Safety and Security DocumentationIdiomaTipo de ArquivoTamanho do Arquivo
Manual de instruçõesPORPDF168 KB
Safety instructions standstill controller KFD2-SR2-**-2.W.SMENGPDF108 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-SR2-Ex2.W.SM

Selecione o Idioma:
CADIdiomaTipo de ArquivoTamanho do Arquivo
CAD 3-D / CAD 3-DALLSTP2510 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ1513 KB

Approvals: KFD2-SR2-Ex2.W.SM

Selecione o Idioma:
CertificatesNúmero do CertificadoIdiomaTipo de ArquivoTamanho do Arquivo
Australia Test SafeANZEx 17.3006XALLPDF6788 KB
Brasil TUV Rheinland BrazilTÜV 13.1125ALLPDF1155 KB
Canada CSACoC 1029981 CALLPDF177 KB
Canada UL cULE106378 cUL (QUZW7)ALLLINK---
China SITIIAS CCC Ex Certificate2020322316001439 (Bintan)ALLPDF1101 KB
DNV MarineTAA00001WXALLPDF106 KB
Europe PTB ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GPTB 00 ATEX 2080ALLPDF554 KB
Europe TUV II 3 GTÜV 99 ATEX 1493XALLPDF2538 KB
India PESO (India) CCOEA/P/HQ/KA/104/6069 (P574609)ALLPDF101 KB
Korea KOSHA09-AV4BO-0222-1ALLPDF346 KB
PTB IECEx Certificate of ConformityIECEx PTB 11.0034ALLLINK---
South Africa MASCMASC S/22-8373XALLPDF713 KB
South Africa MASCMASC MS/17-0863ALLPDF730 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 19.0013XALLLINK---
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20160608 - E106378 RepRef 19970520ALLPDF246 KB
USA FMFM 19 US 0207XALLPDF350 KB
USA ULE106378 UL (QUZW)ALLLINK---
Ukraine SERTIS ExSC 21.0646 XALLPDF12351 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 21UKEX2786ALLPDF141 KB
exida Functional Safety AssessmentP+F 04/03-14 R017ALLPDF148 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF165 KB
Control drawing FM / Control drawing FM   ALLPDF130 KB
Control drawing CSA / Control drawing CSA   ALLPDF159 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0170DALLPDF65 KB

Produtos Relacionados: KFD2-SR2-Ex2.W.SM

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
1-channel, Dry contact input, For line fault detection (LFD)pa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.