Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Faça o download das folhas de dados em PDF:
Folhas de dados: Dados técnicos do
Z728
General specifications |
Type | DC version, positive polarity |
Electrical specifications |
Nominal resistance | 300 Ω |
Series resistance | max. 327 Ω |
Fuse rating | 50 mA |
Hazardous area connection |
Connection | terminals 1, 2 |
Safe area connection |
Connection | terminals 7, 8 |
Working voltage | |
| Supply loop | max. 26.9 V |
| Measurement loop | max. 26.5 V at 10 µA |
Conformity |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) |
Relative humidity | max. 75 % , without condensation |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Core cross section | max. 2 x 2.5 ... mm2 |
Mass | approx. 150 g |
Dimensions | 12.5 x 115 x 116 mm (0.5 x 4.5 x 4.6 inch) (W x H x D) |
| Height | 115 mm |
| Width | 12.5 mm |
| Depth | 116 mm |
Construction type | modular terminal housing , see system description |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BAS 01 ATEX 7005 |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Voltage | 28 V |
| Current | 93 mA |
| Power | 650 mW |
Supply | |
| Maximum safe voltage | 250 V |
Series resistance | min. 301 Ω |
Certificate | TÜV 99 ATEX 1484 X |
| Marking | II 3G Ex nA IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
FM approval | |
| Control drawing | 116-0118 |
UL approval | |
| Control drawing | 116-0139 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx BAS 09.0142 IECEx BAS 17.0091X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
ECLASS 13.0 | 27211016 |
ECLASS 12.0 | 27211016 |
ECLASS 11.0 | 27211016 |
ECLASS 10.0.1 | 27219001 |
ECLASS 9.0 | 27219001 |
ECLASS 8.0 | 27219001 |
ECLASS 5.1 | 27210702 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC002653 |
UNSPSC 12.1 | 39121018 |
Details:
Z728
Product Documentation:
Z728
Design / Simulation:
Z728
Produtos Relacionados:
Z728
Matching System Components |
|
|
|
Accessory Zener Barriers, For individual grounding through insulated mountingpa |
|
|
|
|
Accessory Zener Barriers, For equipotential bonding via the standard railpa |
|
|
|
|
Accessory Zener Barriers, For group grounding through insulated mountingpa |
|
|
|
|
Accessory Zener Barriers, Accessory Surge Protection, For individual grounding through insulated mountingpa |
|
|
|
|
Accessory Zener Barriers, Accessory Surge Protection, For individual grounding through insulated mounting, Packaging unit: 10 piecespa |
|
|
|
|
Accessory Zener Barriers, For individual grounding through insulated mounting, Packaging unit: 10 piecespa |
|
|
|
|
Accessory Zener Barriers, For equipotential bonding via the standard railpa |
|
|
|
|
Accessory Zener Barriers, For individual grounding through insulated mounting, Packaging unit: 1 piecepa |
|
|
|
|
Accessory Zener Barriers, Accessory Surge Protection, For individual grounding through insulated mountingpa |
|
|
|
|
Accessory Zener Barriers, Accessory Surge Protection, For equipotential bonding via DIN mounting railpa |
|