General specifications |
Signal type | Analog input/analog output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Systematic capability (SC) | SC 3 |
Supply |
Connection | Power Rail or terminals 9+, 10- |
Rated voltage | 19 ... 30 V DC |
Ripple | max. 10 % |
Rated current | max. 88 mA at 24 V |
Power dissipation | max. 1.4 W |
Power consumption | max. 2.1 W |
Analog input |
Number of channels | 2 |
Suitable field devices | 2-wire SMART transmitters |
Signal | 0/4 ... 20 mA , limited to approx. 30 mA |
Field circuit | terminals 1+, 2-, 3+, 4- |
Available voltage | min. 15 V at 20 mA min. 18 V at 4 mA |
Control circuit | terminals 5-, 6+; 7-, 8+ |
Input voltage | Voltage across terminals 10 ... 30 V. If the current is supplied from a source > 24 V, series resistance of ≥ (V - 24)/0.02 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 10)/0.02 Ω. (sink output) |
Load | max. 350 Ω (source output) |
Ripple | 20 mV eff |
Analog output |
Number of channels | 2 |
Suitable field devices | SMART I/P converters (positioner), on-site-displays |
Signal | 0/4 ... 20 mA , limited to approx. 30 mA |
Field circuit | terminals 1+, 2-, 3+, 4- |
Load | max. 650 Ω |
Voltage | min. 13 V at 20 mA |
Ripple | 20 mV eff , on all signal terminals |
Control circuit | terminals 5-, 6+; 7-, 8+ |
Voltage drop | max. 6 V |
Line fault detection | > 100 kΩ at max. 30 V, with field wiring open |
Transfer characteristics |
Deviation | max. 20 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
| Influence of ambient temperature | < 2 µA/K (-40 ... 70 °C (-40 ... 158 °F)) |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
Settling time | max. 200 ms |
Rise time/fall time | max. 100 ms (10 ... 90 %) |
Galvanic isolation |
Field circuit/control circuit | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Control circuit/control circuit | functional isolation, rated voltage: 50 V |
Field circuit/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Control/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LED |
Factory setting | analog input with source output |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
Degree of protection | IEC 60529 |
Ambient conditions |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 115 g |
Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 |
| Height | 124 mm |
| Width | 12.5 mm |
| Depth | 114 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | UL 22 ATEX 2786 X |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Output | Ex ia, Ex iaD |
| Voltage | 25.2 V |
| Current | 100 mA |
| Power | 630 mW |
| Internal capacitance | 1.05 nF |
| Internal inductance | 0 |
Supply | |
| Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) |
Input | |
| Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) |
Certificate | UL 22 ATEX 2787 X |
| Marking | II 3G Ex ec IIC T4 Gc [device in zone 2] |
Galvanic isolation | |
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Field circuit/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018 |
International approvals |
IECEx approval | |
| IECEx certificate | IECEx ULD 22.0020X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |