Serviceline Industrial Sensors
Phone: 330-486-0001
Fax: 330-405-4710
Serviceline Explosion Protection
Phone: 330-486-0002
Fax: 330-963-5827

Switch Amplifier HiC2842

HiC2842
  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Dry contact or NAMUR inputs
  • 2 passive transistor outputs
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiC2842

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 30 mA
Power dissipation≤ 600 mW
Power consumption≤ 700 mW
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Rated valuesacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratiomin. 100 µs / min. 100 µs
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Rated voltage30 V DC
Rated current50 mA
Response time≤ 200 µs
Signal level1-signal: (external voltage) - 1 V max. for 50 mA (Tamb = 25 °C (77 °F))
0-signal: blocked output (off-state current ≤ 10 µA)
Output Isignal ; Transistor
Output IIsignal ; Transistor
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Switching frequency≤ 5 kHz
Galvanic isolation
Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Output/Outputbasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Factory settinginput close, transistor closed, lead fault detection enabled
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Galvanic isolationEN 50178:1997
Electromagnetic compatibilityNE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Protection against electrical shockIEC 61140
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humidity≤ 90 % , non-condensing
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1 and 2 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateBVS 09 ATEX E 157
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia, Ex iaD
Voltage10.5 V
Current17.1 mA
Power45 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 50303:2000
International approvals
UL approvalE106378
Control drawing116-0331
IECEx approval
IECEx certificateIECEx BVS 09.0060
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2842

Function

This isolated barrier is used for intrinsic safety applications.

The device transfers digital signals ( NAMUR sensors/mechanical contacts) from the explosion-hazardous area to the non-explosion-hazardous area.

Each input controls a passive transistor for the non-explosion-hazardous area load.

Via switches the mode of operation can be reversed and the line fault detection can be switched off.

During a fault state, the transistors revert to their de-energized state and LEDs indicate the fault according to NAMUR  NE 44. A separate fault bus is available. This fault bus can be monitored if the termination board supports a module fault detection.

This device mounts on a HiC termination board.

Product Documentation: HiC2842

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF160 KB
Functional Safety ManualENGPDF1972 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2842

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiC2842

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
China SITIIAS CCC Ex Certificate2020322316001424 (Singapore)ALLPDF1044 KB
Europe DEKRA EXAM II (1) D I (M1) II (1) GBVS 09 ATEX E 157ALLPDF1314 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC E106378 Rep Ref E106378-20111027ALLPDF565 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 21UKEX21402ALLPDF152 KB
Worldwide DEKRA EXAM IECEx Certificate of ConformityIECEx BVS 09.0060ALLLINK---
exida Functional Safety AssessmentP+F 09/05-5R1C R011 V1R0ALLPDF370 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF136 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0929DALLPDF81 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-5841ALLPDF76 KB

Associated Products: HiC2842

Accessory of
System board for Yokogawa CENTUM VP, For 32-channel DI card ADV151, For 16 modules, Recommended modules: HiC2822 (DI), HiC2842 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Schneider, Foxboro FBM series, For 16 modules, For 32-channel DI card FBM217, 24 V DC supply, Recommended modules: HiC2822 (DI), HiC2842 (DI), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Foxboro, Control system type: FBMpa
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel DI card 3506X, For 16 modules, 24 V DC supply, Recommended modules: HiC2822 (DI), HiC2842 (DI), Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon CXpa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.