Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Descargue la hoja de datos completa en PDF:
Descripción del producto |
---|
I/O hub with IO-Link interface for 16 digital inputs |
Indicators/operating means | ||
---|---|---|
LED PWR | LED green: flashing with short break (1 Hz) - IO-Link mode | |
LED IO | Switch state (IO); multicolor LED yellow: only IO pin 4 is active blue: only IO pin 2 is active green: both IO pin 4 and pin 2 are active red: overload at sensor supply or output |
|
Electrical specifications | ||
Operating voltage | 18 ... 30 V DC, PELV Current limitation of the supply max. 4 A |
|
No-load supply current | ≤ 25 mA | |
Operating current | max. 4 A | |
Interface | ||
Interface type | IO-Link | |
IO-Link revision | 1.1 | |
Device profile | Identification and Diagnosis - I&D Firmware update |
|
Process data | Inputs 3 Byte - Input signals 16 Bit - diagnosis signals 5 Bit |
|
Vendor ID | 1 (0x0001) | |
Device ID | 985857 (0x0F0B01) | |
Data transfer rate | COM3 (230.4 kbits/s) | |
Min. cycle time | 1 ms |
|
SIO mode support | no | |
Compatible master port type | Class A |
|
Input | ||
Number/Type | 16 Inputs for 3-wire sensors (PNP), DC (IN1 ... IN16) | |
Supply | from IO-Link | |
Current loading capacity | 180 mA , overload and short-circuit protected | |
Input current | ≤ 5 mA (limited internally) | |
Switching point | Type 3 according to IEC 61131-2 | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 EN 55011:2016 |
|
Conformity | ||
Communication interface | IEC 61131-9:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 61131-9:2013 | |
Input | EN 61131-2:2007 | |
Communication interface | IEC 61131-9 / IO-Link V1.1.4 | |
Emitted interference | EN 61000-6-4:2007 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006 | |
Approvals and certificates | ||
UL approval | Load specification DC General Use / DC Pilot Duty Degree of protection not tested by UL; tested by Pepperl+Fuchs SE |
|
Ambient conditions | ||
Ambient temperature | -30 ... 70 °C (-22 ... 158 °F) | |
Storage temperature | -30 ... 70 °C (-22 ... 158 °F) | |
Relative humidity | 85 % non-condensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 5000 m above MSL | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm / 5 g 5 ... 500 Hz | |
Pollution degree | 3 | |
Mechanical specifications | ||
Degree of protection | IP67 / IP68 / IP69k | |
Connection | IO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded) Female connector: LF type or similar IN: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, socket contacts, screw-locking, A-coded) Mating connector: LM type or similar |
|
Material | ||
Housing | PBT | |
Mass | 110 g | |
Tightening torque, cable gland | 0.4 Nm (M12 connector), 0.2 Nm (M8 connector) |
|
Dimensions | ||
Height | 29.35 mm | |
Width | 30 mm | |
Length | 143 mm | |
Mounting | screw mounting |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
Parameter Information | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|
IO-Link Parameter Datasheet ICA-16DI-G16-IO | ENG | 338 KB |
Declaration of Conformity | Número de Certificado | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|---|
EU Declaration of Conformity (P+F) | TDOC-7805_SPA | SPA | 194 KB | |
UK Declaration of Conformity (P+F) | TDOC-7806_ENG | ENG | 171 KB |
Device Description Files/Drivers | Liberar Info | Tipo de archivo | Tamaño |
---|---|---|---|
IODD for ICA-16DI-G16-IO / IODD für ICA-16DI-G16-IO | V1.00.000 / 2024-10-25 | ZIP | 215 KB |
Software Tools | |||
IO-Link Offline Parameterization Tool / IO-Link Offline-Parametriertool | V1.00.006 / 2022-07-10 | ZIP | 96138 KB |
Módulo de armario de conmutación AS-Interface KE5 – Manejo sencillo y manipulación mejorada