Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones

AS-Interface sensor/actuator module VBA-4E4A-G12-XEL

VBA-4E4A-G12-XEL
  • One-piece housing with stainless steel base
  • Installation without tools
  • Metal threaded inserts with SPEEDCON technology
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Communication monitoring, configurable
  • Inputs for 2- and 3-wire sensors
  • DIN rail mounting
  • Sensor supply powered by AUX
  • Input and output connection on each M12 connector

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  VBA-4E4A-G12-XEL

Descripción del producto
G12 flat module, 4 inputs (PNP) and 4 electronic outputs
General specifications
Node typeA/B node
AS-Interface specificationV3.0
Required gateway specification≥ V3.0
ProfileS-7.A.7
IO code7
ID codeA
ID1 code7
ID2 code7
UL File NumberE223772
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or outputs
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 4 LED yellow
Electrical specifications
Auxiliary voltage24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom external auxiliary voltage UAUX
Current loading capacity≤ 500 mA overload and short-circuit resistant
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 6 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Voltage≥ (UAUX - 0.5 V)
Current1 A per output
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Altitude≤ 2000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks
10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree3
Mechanical specifications
Degree of protectionIP67
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Material
HousingPBT
Mass200 g
Tightening torque, cable gland0.4 Nm
Dimensions
Height35 mm
Width57.4 mm
Length118 mm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-4E4A-G12-XEL

Product Documentation: VBA-4E4A-G12-XEL

Seleccionar idioma:
Brief InstructionsIdiomaTipo de archivoTamaño
Instruction leaflet / BeipackzettelALLPDF1013 KB

Design / Simulation: VBA-4E4A-G12-XEL

Seleccionar idioma:
CADIdiomaTipo de archivoTamaño
CAD 3-D / CAD 3-DALLSTP4618 KB

Approvals: VBA-4E4A-G12-XEL

Seleccionar idioma:
CertificatesNúmero de CertificadoIdiomaTipo de archivoTamaño
Canada, USA ULCoC 20141115-E223772ALLPDF342 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0978DALLPDF118 KB

Productos asociados: VBA-4E4A-G12-XEL

Accessories

Blind plug for M12 socketsfa

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
lock for G12 modulefa
Descarga gratuita: Documento técnico sobre protocolos de comunicación basados en TCP (PDF)

Este documento técnico gratuito en formato PDF compara los diferentes protocolos de comunicación basados ​​en TCP (AMQP, OPC UA, MQTT, REST API) que se han abierto camino y se consideran los habilitadores de IIoT e Industria 4.0. Descárguelo ahora de forma gratuita.

Módulo de armario de conmutación AS-Interface KE5 – Manejo sencillo y manipulación mejorada

El diseño único de la carcasas del nuevo módulo de armario de conmutación KE5 permite una visibilidad superior y simplifica el montaje, cableado y mantenimiento dentro de los armarios de conmutación y cajas de conexiones.

Gama de productos AS-Interface

Conozca la gama completa de los productos AS-Interface.