Línea de servicio de Sensores Industriales
Atención al cliente para protección contra explosiones

AS-Interface analog module VBA-2A-G11-IL-V1

VBA-2A-G11-IL-V1
  • Degree of protection IP68 / IP69K
  • Function display for bus, external auxiliary voltage and outputs
  • Power supply of outputs from the external auxiliary voltage
  • Accuracy ± 0.15 %
  • Integrated shielding
  • Channel-specific output monitoring
  • Communication monitoring

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Descargue la hoja de datos completa en PDF:


Extracto de la hoja de datos: Información técnica del  VBA-2A-G11-IL-V1

Descripción del producto
G11 analog module, 2 analog outputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
ProfileS-7.3.5
IO code7
ID code3
ID1 codeF
ID2 code5
UL File NumberE223772
Indicators/operating means
LED AS-i/FAULTStatus display; multi-colour LED
Green: normal operation
Red: communication fault
Flashing yellow/red: address 0
Flashing green/red: peripheral fault
LED ANALOGStatus of output signal; yellow LED
Yellow: 0 mA ≤ I ≤ 23 mA
Yellow flashing: lead breakage or I > 23 mA
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 35 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Output
Number/Type2 analog outputs (current), 0 ... 20 mA
Supplyfrom AUX
Loadmax. 600 Ω
Current loading capacity≤ 700 mA (signal current + actuator supply) from external bulk power supply UAUX, overload and short-circuit protected
Resolution6 µA
Accuracy0.15 % of full-scale value
Temperature influence1 µA/K
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP68 / IP69K
ConnectionAS-Interface/UAUX: M12 round connector
Outputs: M12 round connector
Material
HousingPBT PC
Mounting screwStainless steel 1.4305 / AISI 303
Mass200 g
Tightening torque, housing screws1.8 Nm
Tightening torque, cable gland0.4 Nm
Dimensions
Height35 mm
Diameter85 mm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001596
ETIM 8.0EC001596
ETIM 7.0EC001596
ETIM 6.0EC001596
ETIM 5.0EC001596
UNSPSC 12.139121535

Details: VBA-2A-G11-IL-V1

Informative Literature: VBA-2A-G11-IL-V1

Seleccionar idioma:
LiteratureIdiomaTipo de archivoTamaño
Application Report - Automating Material Handling Systems for Airports with AS-InterfaceENGPDF272 KB

Product Documentation: VBA-2A-G11-IL-V1

Seleccionar idioma:
Brief InstructionsIdiomaTipo de archivoTamaño
Instruction leaflet / BeipackzettelALLPDF803 KB
Manuals
Manual VBA-2A-G11-I* & VBA-4A-G11-I/U-FENGPDF3049 KB

Approvals: VBA-2A-G11-IL-V1

Seleccionar idioma:
CertificatesNúmero de CertificadoIdiomaTipo de archivoTamaño
Canada, USA ULCoC 20141115-E223772ALLPDF342 KB
Worldwide AS-International Association AS-Interface95304ALLPDF109 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2931BALLPDF119 KB

Productos asociados: VBA-2A-G11-IL-V1

Accessories

AS-Interface Handheld with accessoryfa

Blind plug for M12 socketsfa
Descarga gratuita: Documento técnico sobre protocolos de comunicación basados en TCP (PDF)

Este documento técnico gratuito en formato PDF compara los diferentes protocolos de comunicación basados ​​en TCP (AMQP, OPC UA, MQTT, REST API) que se han abierto camino y se consideran los habilitadores de IIoT e Industria 4.0. Descárguelo ahora de forma gratuita.

Módulo de armario de conmutación AS-Interface KE5 – Manejo sencillo y manipulación mejorada

El diseño único de la carcasas del nuevo módulo de armario de conmutación KE5 permite una visibilidad superior y simplifica el montaje, cableado y mantenimiento dentro de los armarios de conmutación y cajas de conexiones.

Gama de productos AS-Interface

Conozca la gama completa de los productos AS-Interface.