Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Descargue la hoja de datos completa en PDF:
Descripción del producto |
---|
AS-Interface EMERGENCY STOP button |
General specifications | ||
---|---|---|
Node type | Safety node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
Profile | S-7.B | |
IO code | 7 | |
ID code | B | |
ID1 code | F | |
ID2 code | 0 | |
UL File Number | E305142 | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Performance level (PL) | PL e | |
Category | Cat. 4 | |
Reaction time | < 300 µs | |
MTTFd | no significant contribution to MTTFd of the overall system | |
PFHd | no significant contribution to PFH of the overall system | |
B10d | 250000 cycles | |
Design lifetime | 20 a | |
Indicators/operating means | ||
Button | ||
EMERGENCY STOP | illuminated | |
Electrical specifications | ||
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 80 mA | |
Protection class | III | |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) | |
Rated insulation voltage | 32 V | |
Pulse withstand voltage | 0.8 kV | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | IEC 62026-2:2013 EN 61000-6-2:2005 EN 61000-6-4:2007 A1:2011-02 EN 61326-1:2013 | |
Machinery Directive | ||
Directive 2006/42/EC | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 EN 60947-5-5:1997+A1:2005+A11:2013+A2:2017 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Electrical safety | IEC 61140:2009 | |
Emitted interference | EN 61000-6-4:2007 A1:2011-02 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | IEC 62026-2:2013 EN 61326-3-1:2017 EN 61000-6-2:2005 | |
Functional safety | EN ISO 13849-1:2015 EN ISO 13849-2:2012 EN 62061:2005 + AC:2010 + A1:2013 + A2:2015 EN 60947-5-5:1997+A1:2005+A11:2013+A2:2017 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 5000 m above MSL | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 2000 Hz, 10 cycles | |
Pollution degree | 2 | |
Mechanical specifications | ||
Operating force | Push: 32 N Pull: 21 N Turn: 0.27 Nm Minimum for positive opening operation: 60 Nm |
|
Operating distance | for positive opening operation: min. 4 mm maximal: 4.5 mm |
|
Degree of protection | IP65 |
|
Connection | M12 round connector | |
Material | ||
Housing | Polycarbonate | |
Mass | 225 g | |
Dimensions | ||
Height | 91.5 mm | |
Width | 76 mm | |
Length | 76 mm | |
Life span | > 250,000 switching operations |
System | Classcode |
---|---|
ECLASS 13.0 | 27371244 |
ECLASS 12.0 | 27371244 |
ECLASS 11.0 | 27371244 |
ECLASS 10.0.1 | 27371244 |
ECLASS 9.0 | 27371244 |
ECLASS 8.0 | 27371244 |
ECLASS 5.1 | 27371228 |
ETIM 9.0 | EC002034 |
ETIM 8.0 | EC002034 |
ETIM 7.0 | EC002034 |
ETIM 6.0 | EC002034 |
ETIM 5.0 | EC002034 |
UNSPSC 12.1 | 39121533 |
CAD | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 873 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Accessories | ||||||
---|---|---|---|---|---|---|
|